Specifications

Graphic Operation Terminal GOT-F900 Creation of Display Screens (FX-PCS-DU/WIN-E) 18
18-2
Data display objects: Display the contents of devices in the PLC.
Object name Description Use example
Library Text
Displays text stored in the text library.
The text to be displayed can be specified using a word device (T,
C, D, V or Z).
---
Number
Displays a word device (current value/set value of timer/counter or
D, V or Z) in the PLC in a specified position for monitoring.
c)
Bar Graph
Displays a word device (current value/set value of timer/counter or
D, V or Z) in the PLC in a specified position in the form of bar
graph for monitoring.
d)
Circle Graph
Displays a word device (current value/set value of timer/counter or
D, V or Z) in the PLC in a specified position in the form of circle
graph for monitoring.
---
Proportional Bar
Graph
Displays up to 8 consecutive word devices in the form of a
proportional bar graph.
---
Proportional Pie
Graph
Displays up to 8 consecutive word devices in the form of a
proportional pie graph.
---
Panel Meter
Displays a word device in the form of panel meter. ---
Indicator
Inverts a specified area on the screen by setting a bit device in the
PLC ON or OFF.
---
Label Indicator
Displays specified characters when a specified bit device
becomes ON.
---
Text Indicator
Displays two types of texts alternately in accordance with the ON/
OFF status of a bit device in the PLC. Texts stored in the text
library can be specified for display.
---
Image Indicator
Displays two types of images alternately in accordance with the
ON/OFF status of a bit device in the PLC. Images stored in the
image library can be specified for display.
---
Overlay Screen
Allows a specified screen to overlay another screen when a bit
device in the PLC becomes ON or OFF.
---
Library Image
Displays an image stored in the image library. The image can be
specified using a word device (T, C, D, V or Z).
---
Trend Graph
Displays word devices in the PLC sampled at a constant time
interval in the form of trend graph. Up to 4 devices can be
displayed.
---
Line Graph
Acquires data stored in a word device at each specified timing,
displays a line graph of the acquired data within the display range,
then allows scroll of the line graph.
---
Ascii
Allows a character code to be specified from the PLC, and
displays a corresponding character such as alphabet, numeric.
ASCII code is available as character codes.
---