Specifications
Graphic Operation Terminal GOT-F900 Alarm MODE 10
10-12
2) Reset operation
An occurred alarm (auxiliary relay in the ON status) can be reset to OFF.
Place the cursor on an alarm to be reset using the scroll keys, and press the RESET key 4).
When the alarm device (auxiliary relay) is reset, the corresponding alarm message is
deleted from the list.
However, when the RESET key is set together with the ACK key, the corresponding alarm
message in the list is not deleted even if the alarm device is set to OFF. In such a case,
perform the confirmation operation described above.
In the sequence program shown below in which an auxiliary relay turns ON again even if it
is set to OFF once by the reset operation, the alarm device cannot be reset to OFF.
For example, if M100 is reset to OFF, M100 will turn ON again if
the contact **** is ON.
Change the program so that the contact **** which causes the
alarm device M100 to turn ON is set to OFF.
* To make the reset operation effective, make sure to set the reset function effective in
alarm setting in the screen creation software.
3) Detail display (valid when GT Designer is used)
The alarm message list (comment window) or the base screen can be changed to the
detailed display.
To enable detailed display, "Detail Display Destination" in "Alarm History Common Setting"
in the screen creation software should be set to "Comment Window" or "Base Screen".
• When "Comment Window" is selected
• Place the cursor on an alarm message, and press the
DETAIL key. Then, the detailed display window is open
as shown on the left.
• Comments which are created in "Comment Creation" and
specified by "Comment No." in "Alarm History Common
Setting"
–
"Device Monitor"
–
"Edit" are displayed.
* When FX-PCS-DU/WIN-E is used, comments in the alarm list are displayed.
• When "Base Screen" is selected
The specified screen in "Detail Display No." in "Alarm History Common Setting"
–
"Device
Monitor"
–
"Edit" is displayed.
****
ON
M100
Alarm has
occurred.
M100
DETAIL
When this button is pressed, the
detailed display window is closed.