Specifications

Graphic Operation Terminal GOT-F900 USER SCREEN MODE 7
7-29
7.8 Numeric setting completion flag and data changing flag
When data is being changed for "Number" ("Numerical Input") or "Ascii" ("Ascii Input") or the
procedure is complete, the following devices turn ON.
At this time, the ID code is written to the PLC so that a device whose data is changed can be
identified.
The numeric setting completion flag and data changing flag can be used in data change by
both touch key and key-pad.
When FX-PCS-DU/WIN-E is used
1) Completion flag
When a screen is created using the FX-PCS-DU/WIN-E, a control device (described in
Section 6.6.1) M
&
+5 turns ON as the completion flag.
Interface device
•M
&
+5
"
&
" indicates the head control device number.
For example, when the head control device is set to M10, M15 functions as the numeric
setting completion flag.
* Control devices can be set using the screen creation software.
Operation
When a current or set value of a word device is changed using the following objects, the
flag turns ON.
Object names: "Data Change" and "Keyboard"
(The flag does not turn ON when the "Data+1", "Data-1" or "Constant"
object is used.)
ON timing : The flag turns ON when the ENT key of the "Data Change" or "Keyboard"
object is pressed. The flag does not turn ON when any other key is pressed.
While the touch key code is set to "000D" (Write to destination device: Execute), M
&
+5
turns ON in the same way when the touch key is pressed.
Once the completion flag turns ON, the ON status is held. In order to turn it OFF, execute
the RST (RESET) instruction using the program in the PLC.
2) User ID
The user ID is assigned to each "Number" and "Ascii" in the order of creation.
The user ID is assigned from "1" on each screen. When data is changed, the user ID is
written to the control device D
&
+7.