Specifications
Item
Model ESA30E-25
Power supply 3-phase 380V ±5% / 400V ±5% / 415V ±5% 50Hz
Operation to top up
(In intermediate season)
*
1
Heating capacity kW 30
Water amount Liter/min 8.97
Power consumption kW 6.98
COP – 4.3
Operation to top up
(In cold region)
*
2
Heating capacity kW 30
Water amount Liter/min 5.06
Power consumption kW 10.73
COP – 2.8
Operating sound
*
3
dB(A) 58
Outside dimension
Height mm 1,690
Width mm 1,350
Depth mm 720 + 35 (Water pipe connection)
Current
Max A 21
Starting A 5
Unit weight kg 375 (During operation 385)
Retained water amount L 10
Color Stucco white (4.2Y7.5/1.1 approx.)
Compressor
Type × Pcs Hermetic inverter compressor × 1
Nominal output kW 6.4
Refrigerant
Type R744 (CO2)
Charged amount kg 8.5
Refrigerant oil
Type MA68
Charged volume cc 1200
Crankcase heater W 20
Anti-freezing heater
for water pipe W 48 × 3
for drain pan W 40 × 2
for drain hose W 40 × 2 + 48
Heat exchanger, Air side Copper pipe straight fin type
Heat exchanger, Water side(Gas cooler) Copper pipe coil type
Fan
Type Axial flow type (direct coupled motor) × 2
Output × Pcs W 386 × 2
Air volume m
3
/min 260
Water pump
Type × output Non-self-suction spiral type inverter pump × 100W
Materials contacting to water Bronze, SCS13
Actual pump head m (kPa) 5m (49kPa) @17Liter/min
Usage temp range
Outdoor air temp °C –25 to +43
Feed water inlet temp °C 5-63
Hot water outlet temp °C 60-90
Water pressure range kPa 500 or lower
Defrost Hot gas type
Vibration and sound proofing devices
Compressor: placed on anti-vibration rubber and wrapped with sound insulation
Protection devices
High pressure switch, over current protection, power transistor overheat
protection and anomalous high pressure protection
Pipe size
Feed water inlet Rc3/4 (Copper 20A)
Hot water outlet Rc3/4 (Copper 20A)
Drain water outlet Rc3/4 (Copper 20A)
Electric wiring
Earth leakage breaker 30A, 30mA, 0.1sec
Power cable size
□
14 × 4 (Length 40m)
Moulded-case circuit breaker Rated corrent: 30A, switch capacity: 30A
Grounding wire size M6
Remote controller wire size 0.3mm
2
× 2cores shielding wire (MVVS)
Design pressure MPa High pressure: 14.0, Low pressure: 8.5
IP code IP24
(Note)
1. Performance of operation to top up in intermediate season shows the capacity measured under the conditions that outdoor air temp is 16°C
DB/12°C WB, water inlet temp is 17°C and hot water outlet temp is 65°C.
2. Performance of operation to top up in cold region shows the capacity measured under the conditions that outdoor air temp is –7°C DB/–8°C WB,
water inlet temp is 5°C and hot water outlet temp is 90°C excluding heater for anti-freezing water (345W).
3. Operating sound shows a value measured at 1m in front of the unit and 1m above the floor in anechoic room where the sound is resonated a little.
Accordingly if the unit is installed on actual site, it is normal that the measured sound there is higher than the value shown above, because it is
influenced by surrounding noise and echo in the room.
4. The actual hot water outlet temp may vary ±3°C from target temp according to the change of outdoor
air temp and water inlet temp. And then if feed water inlet temp is 30°C or higher and outdoor air temp
is 25°C or higher, hot water outlet temp may be controlled not to increase too high.
5. Please use the clean water. The water quality should follow a guideline of JRA-GL. 02:1994.
If the water quality is out of the standard, it may cause troubles such as scale buildup and/or corrosion.
6. These articles mentioned above may vary without any notice according to the development status.
Fixing heat pump unit
Anchor bolt M10 × 4
According to the installation conditions,
please take a measure to prevent from
falling, cross wind and heavy snow.