Specifications

6 - 22 6 - 22
6. HOW TO COMMUNICATE WITH ID TAGS
6.4.5 Program example with QnACPU use
Set the parameters using "Network Parameters" of GX Developer.
(1) Parameter settings
(a) Setting the network parameters
Table 6.10 "CC-Link List Settings" Dialog Box Settings (with QnACPU Use)
Set Item Set Value
No. of boards in module 1 (module)
Start I/O No. 0000
Type Master station
All connect count 1 (station)
Remote input (RX) refresh device X1000
Remote output (RY) refresh device Y1000
Remote register (RWr) refresh device D1100
Remote register (RWw) refresh device D1000
Special relay (SB) refresh device B0
Special register (SW) refresh device W0
Retry count 3 (times)
Automatic reconnection station count 1 (module)
Wait master station No. 0
PLC down select Stop
Scan mode setting Asynchronous
Delay information setting 0
Station information setting Refer to Section (1) (b) in this section.