Specifications
6 - 20 6 - 20
6. HOW TO COMMUNICATE WITH ID TAGS
(b) Setting the network parameters
Table 6.8 "CC-Link List Settings" Dialog Box Settings (with LCPU Use)
Set Item Set Value
Number of Modules 1 (module)
Start I/O No. 0000
Type Master Station
Mode Remote Net(Ver.1 Mode)
Transmission speed 156kbps
Total Module Connected 1 (station)
Remote input (RX) refresh device X1000
Remote output (RY) refresh device Y1000
Remote register (RWr) refresh device D1100
Remote register (RWw) refresh device D1000
Special relay (SB) refresh device SB0
Special register (SW) refresh device SW0
Retry Count 3 (times)
Automatic Reconnection Station Count 1 (module)
Standby Master Station No. No setting
PLC Down Select Stop
Scan Mode Setting Asynchronous
Delay Time Setting 0
Station Information Setting Refer to Section (1) (c) in this section.
Remote Device Station Initial Setting Refer to Section 6.4.3 (2).
Interrupt Setting No setting