4. SETUP AND PROCEDURES PRIOR TO OPERATION
4.7 Wiring
The following describes the wiring of the RFID interface module.
4.7.1 Wiring precautions
CAUTION
Do not wire the cables near or bundle the cables with main circuit cables or
power lines. Doing so causes noise and surge impact, resulting in the risk of
malfunction. At the very least, separate the module cables from the above by
100mm or more.
Be sure to ground the FG terminal using programmable controller dedicated
class D (type 3) grounding or greater. Failure to do so results in the risk of
electric shock and malfunction.
Do not invert the external power supply polarities +24V and 24G. The RFID
interface module will not operate.