Specifications

4 - 9 4 - 9
4. SETUP AND PROCEDURES PRIOR TO OPERATION
No. Name Description
2)
Station number
setting switch
Used to set the 10's place of the station number using station numbers "10", "20", and "40".
Used to set the 1's place of the station number using station numbers "1", "2", "4", and "8".
Always set the station number within the range of 1 to 64.
When a value is set outside of the range 1 to 64, an error occurs and the "L ERR." LED
turns on.
Duplicate station numbers cannot be set.
Station
No.
10's Place 1's Place
40 20 10 8 4 2 1
1 OFF OFF OFF OFF OFF OFF ON
2 OFF OFF OFF OFF OFF ON OFF
3 OFF OFF OFF OFF OFF ON ON
4 OFF OFF OFF OFF ON OFF OFF
: : : : : : : :
10 OFF OFF ON OFF OFF OFF OFF
11 OFF OFF ON OFF OFF OFF ON
: : : : : : : :
64 ON ON OFF OFF ON OFF OFF
(Example) When the station number is set to "32", the switch is set as follows.
Station
No.
10's Place 1's Place
40 20 10 8 4 2 1
32 OFF ON ON OFF OFF ON OFF
3)
Transmission
speed setting
switch
Set Value
Setting Switch
Transmission
Speed
4 2 1
0 OFF OFF OFF 156kbps
1 OFF OFF ON 625kbps
2 OFF ON OFF 2.5Mbps
3 OFF ON ON 5Mbps
4 ON OFF OFF 10Mbps
Always set the transmission speed in the range above.
All settings at the time of shipment are OFF.
When a setting other than the above is set, an error occurs and the "L ERR." LED turns on.
4)
Transmission
/module power
supply terminal
block
The module power supply and transmission terminal block.
Terminal Name Overvie
w
DA
CC-Link dedicated cable terminal
DB
DG
SLD
FG Class D (type 3) grounding terminal
+24V
External power supply terminal
24G
ON
ON