Specifications
3 - 12 3 - 12
3. SPECIFICATIONS
*1. The last address is as follows according to the mode switch setting.
Table 3.10 Remote Register Last Address
Mode Switch Set
Value
Last Address
Remarks
RWw RWr
0 RWwm+FH RWrm+FH Ver. 1 compatible, 4 occupied stations, RWw/RWr: 16 points each
1 to 3 - - -
4 RWwm+7H RWrm+7H Ver. 1 compatible, 2 occupied stations, RWw/RWr: 8 points each
5 RWwm+FH RWrm+FH
Ver. 2 compatible, 2 occupied stations, Expanded cyclic setting
: Double, RWw/RWr: 16 points each
6 RWwm+1FH RWrm+1FH
Ver. 2 compatible, 2 occupied stations, Expanded cyclic setting
: Quadruple, RWw/RWr: 32 points each
7 RWwm+3FH RWrm+3FH
Ver. 2 compatible, 2 occupied stations, Expanded cyclic setting
: Octuple, RWw/RWr: 64 points each
8 to F - - -
m: Address assigned to master station by station number setting.
*2. The address and contents in RUN mode are as follows according to the mode
switch setting.
Table 3.11 Remote Register Address Range
Mode Switch Set
Value
Address Description
Remarks
0
RWwm+3H to RWwm+FH Write data specification areas 1 to 13
Ver. 1 compatible, 4 occupied
stations, 13 points (26 bytes)
RWrm+3H to RWrm+FH Read data storage areas 1 to 13
1 to 3 - - -
4
RWwm+3H to RWwm+7H Write data specification areas 1 to 5
Ver. 1 compatible, 2 occupied
stations, 5 points (10 bytes)
RWrm+3H to RWrm+7H Read data storage areas 1 to 5
5
RWwm+3H to RWwm+FH Write data specification areas 1 to 13
Ver. 2 compatible, 2 occupied
stations, Expanded cyclic setting
: Double, 13 points (26 bytes)
RWrm+3H to RWrm+FH Read data storage areas 1 to 13
6
RWwm+3H to RWwm+1FH Write data specification areas 1 to 29
Ver. 2 compatible, 2 occupied
stations, Expanded cyclic setting
: Quadruple, 29 points (58 bytes)
RWrm+3H to RWrm+1FH Read data storage areas 1 to 29
7
RWwm+3H to RWwm+3FH Write data specification areas 1 to 61
Ver. 2 compatible, 2 occupied
stations, Expanded cyclic setting
: Octuple, 61 points (122 bytes)
RWrm+3H to RWrm+3FH Read data storage areas 1 to 61
8 to F - - -
m: Address assigned to master station by station number setting.