Specifications
3 - 3 3 - 3
3. SPECIFICATIONS
Point
Each of the following conditions must be satisfied:
(1) In remote net Ver.1 mode
Condition 1
{(1×a) + (2×b) + (3×c) + (4×d)} ≤ 64
a: Number of modules with one occupied station
b: Number of modules with two occupied stations
c: Number of modules with three occupied stations
d: Number of modules with four occupied stations
Condition 2
{(16×A) + (54×B) + (88×C)} ≤ 2304
A: Number of remote I/O stations ≤ 64 stations
B: Number of remote device stations ≤ 42 stations
C: Number of local stations, standby master stations, and intelligent device stations ≤ 26 stations
(2) In remote net Ver.2 mode and remote net additional mode
Condition 1
{(a + a2 + a4 + a8) + (b + b2 + b4 + b8) ×2 + (c + c2 +c4 + c8) ×3+ (d + d2 + d4 + d8) ×4}
≤ 64
Condition 2
[{(a×32) + (a2×32) + (a4×64) + (a8×128)} + {(b×64) + (b2×96) + (b4×192) + (b8×384)}
+ {(c×96) + (c2×160) + (c4×320) + (c8×640)} + {(d×128) + (d2×224) + (d4×448) + (d8×896)}]
≤ 8192
Condition 3
[{(a×4) + (a2×8) + (a4×16) + (a8×32)} + {(b×8) + (b2×16) + (b4×32) + (b8×64)}
+ {(c×12) + (c2×24) + (c4×48) + (c8×96)} + {(d×16) + (d2×32) + (d4×64) + (d8×128)}] ≤ 2048
a: Total number of Ver. 1 compatible slave stations with one occupied station and Ver. 2
compatible slave stations with one occupied station set to “Single”
b: Total number of Ver. 1 compatible slave stations with two occupied stations and Ver. 2
compatible slave stations with two occupied stations set to “Single”
c: Total number of Ver. 1 compatible slave stations with three occupied stations and Ver. 2
compatible slave stations with three occupied stations set to “Single”
d: Total number of Ver. 1 compatible slave stations with four occupied station and Ver. 2
compatible slave stations with four occupied stations set to “Single”
a2: Total number Ver. 2 compatible slave stations with one occupied station set to “Double”
b2: Total number Ver. 2 compatible slave stations with two occupied stations set to “Double”
c2: Total number Ver. 2 compatible slave stations with three occupied stations set to “Double”
d2: Total number Ver. 2 compatible slave stations with four occupied stations set to “Double”
a4: Total number Ver. 2 compatible slave stations with one occupied station set to “Quadruple”
b4: Total number Ver. 2 compatible slave stations with two occupied stations set to “Quadruple”
c4: Total number Ver. 2 compatible slave stations with three occupied stations set to “Quadruple”
d4: Total number Ver. 2 compatible slave stations with four occupied stations set to “Quadruple”
a8: Total number Ver. 2 compatible slave stations with one occupied station set to “Octuple”
b8: Total number Ver. 2 compatible slave stations with two occupied stations set to “Octuple”
c8: Total number Ver. 2 compatible slave stations with three occupied stations set to “Octuple”
d8: Total number Ver. 2 compatible slave stations with four occupied stations set to “Octuple”
Condition 4
{(16×A) + (54×B) + (88×C)} ≤ 2304
A: Number of remote I/O stations ≤ 64 stations
B: Number of remote device stations ≤ 42 stations
C: Number of local stations, standby master stations, and intelligent device stations ≤ 26 stations