Specifications

App - 11 App - 11
APPENDICES
The precautions for attaching a noise filter are described below.
Do not bundle the cables on the input side and output side of the noise filter.
If bundled, the output side noise will be induced into the input side cables
from which the noise was filtered.
Ground the noise filter grounding terminal to the control panel with the shortest
cable possible (approx. 10cm (3.94 inches)).
Appendix 4.2 Requirements to compliance with the Low Voltage Directive
This module operates at the rated voltage of 24VDC.
The Low Voltage Directive is not applied to the modules that operate at the rated
voltage of less than 50VAC and 75VDC.
Input side
(power supply side)
Input side
(power supply side)
Filter Filter
Induction
Output side
(device side)
Output side
(device side)
Noise will be induced when the input
and output wires are bundled.
Separately install the input and
output wires.