Electric Heat Kit Installation Manual
Table Of Contents
- Electric Heat Kit
- Table of Contents
- CHECK LIST AFTER INSTALLATION
- Dimensions
- 1. Electric Heat Kit Models
- 2. Electric Heat Kit Accessories
- 3. Safety precautions
- 4. Installing the Electric Heat Kit
- 4.1 Read the safety precautions section of the Multi-Position Air Handler before installing the electric heat option.
- 4.2 Setting proper external static pressure.
- 4.3 Enabling Electric Heat
- 4.4 Operation Mode
- 4.5 Attaching the enclosure to the Air Handler
- 4.6 Proper Support in the Horizontal Position for the Multi-Position Air Handler with Electric Heat Kit:
- 4.7 Rotating circuit breaker orientation for Horizontal Left Installations:
- 5. Electrical Schematics
Table 1-2
Electric Heat
Part Number
Heater
kW
Heater
Amps
1
MCA
1
MOP
1
Htr & Mtr
Amps
2
MCA
2
MOP
2
Factory
Installed
Circuit
Breaker
208V/
240V
208V/240V 208V/240V 208V/
240V
208V/240V 208V/240V 208V/
240V
EH03-SVZ-S 2.3/3.0 10.8/12.5 13.5/15.6 15/20 13.2/14.9 16.5/18.6 20/20 20
EH05-SVZ-S 3.8/5.0 18.1/20.8 22.6/26 25/30 20.5/23.2 25.6/29 30/30 30
EH08-SVZ-S 6.0/8.0 28.9/33.3 36.1/41.7 40/45 31.3/35.7 39.1/44.7 40/45 45
EH05-SVZ-M 3.8/5.0 18.1/20.8 22.6/26 25/30 21.4/24.1 26.7/30.2 30/30 30
EH08-SVZ-M 6.0/8.0 28.9/33.3 36.1/41.7 40/45 32.2/36.6 40.2/45.8 45/50 50
EH10-SVZ-M 7.5/10 36.1/41.7 45.1/52.1 50/60 39.4/45 49.3/56.2 50/60 60
EH03-MPA-S(B) 2.3/3.0 10.8/12.5 13.5/15.6 15/20 13.2/14.9 16.5/18.6 20/20 20
EH05-MPA-S(B) 3.8/5.0 18.1/20.8 22.6/26 25/30 20.5/23.2 25.6/29 30/30 30
EH08-MPA-S(B) 6.0/8.0 28.9/33.3 36.1/41.7 40/45 31.3/35.7 39.1/44.7 40/45 45
EH03-MPA-M(B) 2.3/3.0 10.8/12.5 13.5/15.6 15/20 14.1/15.8 17.7/19.8 20/20 20
EH05-MPA-M(B) 3.8/5.0 18.1/20.8 22.6/26 25/30 21.4/24.1 26.7/30.2 30/30 30
EH08-MPA-M(B) 6.0/8.0 28.9/33.3 36.1/41.7 40/45 32.2/36.6 40.2/45.8 45/50 50
EH10-MPA-M(B) 7.5/10 36.1/41.7 45.1/52.1 50/60 39.4/45 49.3/56.2 50/60 60
EH10-MPA-L(B) 7.5/10 36.1/41.7 45.1/52.1 50/60 40.6/46.2 50.8/57.7 60/60 60
EH15-MPAS-L(B) 11.3/15
Circuit
1
27.1/31.2 33.9/39.1 35/40 31.6/35.8 39.5/44.7 40/45 45
Circuit
2
27.1/31.2 33.9/39.1 35/40 27.1/31.2 33.9/39.1 35/40 40
EH17-MPAS-L(B) 13.2/17.5
Circuit
1
31.6/36.5 39.5/45.6 40/50 36.1/41 45.1/51.2 45/60 60
Circuit
2
31.6/36.5 39.5/45.6 40/50 31.6/36.5 39.5/45.6 40/50 50
1
Heater amps; no motor
2
Heater and motor amps (connect air handler power supply to largest circuit breaker)
60Hz
Motor amps are placed on circuit 1 when required
Unit tested at 0.60 in WG external static pressure
Minimum installation clearance to combustible material 0"
Maximum outlet air temperature 200° F
Electric Heat Kit
Specifications are subject to change without notice. 7 © 2018 Mitsubishi Electric US, Inc.