Electric Heat Kit Installation Manual
Table Of Contents
- Electric Heat Kit
- Table of Contents
- CHECK LIST AFTER INSTALLATION
- Dimensions
- 1. Electric Heat Kit Models
- 2. Electric Heat Kit Accessories
- 3. Safety precautions
- 4. Installing the Electric Heat Kit
- 4.1 Read the safety precautions section of the Multi-Position Air Handler before installing the electric heat option.
- 4.2 Setting proper external static pressure.
- 4.3 Enabling Electric Heat
- 4.4 Operation Mode
- 4.5 Attaching the enclosure to the Air Handler
- 4.6 Proper Support in the Horizontal Position for the Multi-Position Air Handler with Electric Heat Kit:
- 4.7 Rotating circuit breaker orientation for Horizontal Left Installations:
- 5. Electrical Schematics
Available knockouts
Available knockouts
Available knockouts
SVZ
PVFY/PVA/MVZ
Available knockouts
Available knockouts
Available
knockouts
Available
knockouts
Available knockouts
Available knockouts
Available knockouts
Available
knockouts
4.5.K. Power can be provided to the Multi-Position air handler from the electric heat kit by providing power from the
two open terminal connections on the circuit breaker
. For PVFY-A·NAMU-E(1) models incoming power to air handler
will terminate at L1 and L2. For MVZ-A·AA4(7), SVZ-KP-NA and PVA-A·AA4(7) models, the SPTB1 terminal kit must
be installed in the multi-position air handler if the air handler will receive power from the electric heat kit. Please refer
to SPTB1 instructions for proper power connection.
A
USE THE (2) OPEN TERMINAL CONNECTIONS ON THE
SVZ
PVFY/PVA/MVZ
USE THE (2) OPEN TERMINAL CONNECTIONS ON THE
CIRCUIT BREAKER TO POWER THE AIR HANDLER. ONE
ON L1 AND ONE FOR L2.
Detail A
A
A
Use the (2) open terminal connections on the
Circuit breaker to power the air handler. One
On L1 and one for L2.