Electric Heat Kit Installation Manual

4.3 Enabling Electric Heat
PVFY
-A·NAMU-E(1) models:
When installing the Electric Heat Kit on PVFY-A·NAMU-E models, Switch 3-4 on the control board inside the Multi-Position
Air Handler must be “ON”. When installing the Electric Heat Kit on PVFY-A·NAMU-E1 models, Switch 3-2 on the control
board inside the Multi-Position Air Handler must be “ON”. This activates the electric heat option.
SW 3-4
ON
OFF
For PVFY-A·NAMU-E models ONLY
SW 3-2
ON
OFF
For PVFY-A·NAMU-E1 models ONLY
The Electric Heat Lock-out control for PVFY-A·NAMU-E(1) models is set by the outdoor unit. SW5-10 – ON, will Enable the
electric heat lockout. The electric heat lockout will prevent the electric heat from energizing above a set ambient
temperature. The factory setting is 32° F with SW5-10 in the “ON” position. The temperatures can be adjusted by the
Maintenance T
ool to change what ambient temperature the electric heat is locked out. The following table shows the
default values for the Electric Heat Lockout.
These set temperatures can be changed by the Maintenance Tool
Heater Control by
Outdoor Air Temp.
-4F
32F
50F
68F
Electric Heat Kit
Specifications are subject to change without notice. 14 © 2018 Mitsubishi Electric US, Inc.