User`s guide

Hardware
24 Mitsubishi Electric, MA00758A
3.7 Hardware Replacement
This section contains instructions on how to replace operator panel hardware. Only
components included in the latest bill of material and spare parts list are
allowed. See Available Spare Parts.
3.7.1 Mode Switches
The E1000 operator panels have four mode switches (DIP switches) located on the
rear side of the operator panel.
The mode switches have the following functions:
1=ON, 0=OFF
Each letter in “MODE” has a corresponding mode switch
Warning:
The modes below are to be used with caution.
MODE Description for E1012 and E1022
0000 “Run-mode” - Normal operation.
0010 System Restore, resets the file system. Restores the operator panel to factory
settings.
Warning! Information can easily accidently be lost.
0100 Image Load mode (Sysload) allows upgrading of the firmware in the operator
panel.
1000 Service Menu mode, the service menu for the system program is shown.
Allows the user to set IP configuration, erase the project etc. See section 3.8
Service Menu for details.
1110 Self-Test.
1 2 3 4
ON DIP
1
24V DC
CF CARD
COM 1
RS422
RS485
COM 2
RS232
10/100
EXPANSION
BUSY
MODE
1 2 3 4
ON DIP
1 2 3 4
ON DIP
1 2 3 4
ON DIP