ACCESS CONTROL SYSTEM 16670 -12
a. Honeywell
b. PowerSonic
2. Shall be housed in a sealed impact-resistant case
3. Shall be securely mounted in an enclosure
4. Shall be sized to provide 8 hours backup at specified voltage and 120% rated current
draw to all connected devices.
PART 3 - EXECUTION
3.1 INSTALLATION
A. Install system and materials in accordance with manufacturer’s instructions, and as detailed
on the project drawing set.
B. Drawings of the ACMS network are diagrammatic only and any apparatus not shown, but
required to make the system operative to the complete satisfaction of the Architect shall be
furnished and installed without additional cost.
C. Line and low voltage electrical connections to control equipment shown specified or shown
on the control diagrams shall be furnished and installed by this contractor in accordance
with these specifications.
D. Provide initial user account setup, as specified by owner, for a maximum of 20 users.
3.2 WIRING
A. All electrical control wiring and power wiring to the Security Controller, computers and
network components, and all components monitored and controlled by the ACMS shall be
the responsibility of the this contractor.
B. All communication and control wiring shall conform to specifications as provided by the
manufacturer of the ACMS.
C. All wiring shall be in accordance with the Division 16 specifications, the National Electrical
Code and any applicable local codes. All ACMS wiring shall be installed in EMT conduit,
minimum size 3/4”, installed in accordance with the Division 16 specifications. Conduit
routed into door frames shall be minimum size 1/2”.
3.3 WARRANTY
A. Equipment, materials and workmanship incorporated into the work shall be warranted for a
period of one year from the time of system acceptance.
B. Within this period, upon notice by the Owner, any defects in the work provided under this
section due to faulty materials, methods of installation or workmanship shall be promptly
(within 48 hours after receipt of notice) repaired or replaced by this contractor at no expense
to the Owner.