Specifications

St. David Catholic School Manning Architects
Gym and Classroom Replacement N10.024.00
New Orleans, Louisiana July 20, 2012
ACCESS CONTROL SYSTEM 16670 -11
c. Securitron
2. Recessed as specified for each location
3. SPDT contact configuration
4. Operate over normal door opening tolerances
F. Power Supplies / Battery Chargers
1. Manufacturers: Subject to compliance with requirements, provide products by one of the
manufacturers specified.
a. Altronix
b. Honeywell
c. Schlage
d. Securitron
2. UL Listed for Access Control (UL294)
3. Provide 12-15 VDC current limited output.
4. Provide charging for 12 VDC sealed lead-acid batteries.
5. Provide automatic switchover from Primary to Battery power without voltage drop.
6. Provide dry contacts for indication of Low Battery and AC Power Failure.
7. Be selected to provide 120% current capacity.
G. Badging Station
1. Manufacturers: Subject to compliance with requirements, provide products by one of the
manufacturers specified.
H. Enclosures
1. Manufacturers: Subject to compliance with requirements, provide products by one of the
manufacturers specified. If the selected Security Controller requires a specific enclosure
to maintain listings and approvals, use the enclosure specified by the Security Controller
manufacturer.
a. Honeywell
b. Schlage
c. Securitron
2. Provide locking doors. All keys for door locks are to be given to the Owner at job
completion.
3. Provide tamper indication via a door position switch.
4. Clearly labeled with manufacturer’s name and contents.
5. Provide grounding lugs for connection to earth ground and EMI shielding.
I. Batteries
1. Manufacturers: Subject to compliance with requirements, provide products by one of the
manufacturers specified. If the selected Security Controller requires a specific enclosure
to maintain listings and approvals, use the enclosure specified by the Security Controller
manufacturer.