Specifications
St. David Catholic School Manning Architects
Gym and Classroom Replacement N10.024.00
New Orleans, Louisiana July 20, 2012
ACCESS CONTROL SYSTEM 16670 -8
d. Off / Disabled
4. Alarm generation shall be selectable for annunciation type and acknowledgement
requirements:
a. Enable/Disable Alarm indicator
b. Require Notes on Alarm Acknowledgement
5. Alarms shall display the following states:
a. In alarm – point is currently in alarm and has not been acknowledged
b. Acknowledged alarm – point is currently in alarm and has been acknowledged
c. Return to normal – point has returned to normal, but has not been acknowledged
d. Acknowledged normal alarm – point has returned to normal and has been
acknowledged
6. The following types of security alarms shall be generated:
a. Access Event Alarms
1. Door Forced
2. Door Held Open
3. Badge Does Not Exist
4. Badge is Lost
5. Badge is Disabled
6. No Active Schedule
7. No Access Right
8. Granted But Not Used
9. Invalid Pin Number
10. Anti Passback Violation
11. Duress Alarm
12. Access Zone Disabled
13. Access Zone Occupancy Violation
14. Access Zone Supervisor Required
15. Intrusion Zone Armed from intrusion detection system
16. Intrusion Zone Disarmed from intrusion detection system
17. Intrusion Zone Arming Failed from intrusion detection system
18. Intrusion Zone Alarm from intrusion detection system
b. Power Failure
c. Communications Alarm
d. Open Circuit Supervision
e. Short Circuit Supervision
G. Each alarm may have operator instructions assigned to it.
H. Controller and network failures shall be treated as alarms and annunciated.
I. Alarms shall be annunciated in any of the following manners as defined by the user: