Specifications

St. David Catholic School Manning Architects
Gym and Classroom Replacement N10.024.00
New Orleans, Louisiana July 20, 2012
INTRUSION DETECTION SYSTEM 16650 -6
3. Humidity - The system shall be designed for normal operation in an 85% relative
humidity environment.
4. Electromagnetic Interference – The system shall meet or exceed the requirements of
FCC Part 15, Class B devices, FCC Part 68, IEC EMC directive.
2.03 MOTION DETECTOR
A. The motion detector shall be dual technology, microwave, passive infrared, with
adjustable sensitivity and range.
2.05 MAGNETIC CONTACTS
A. Magnetic contacts shall be flush mount, with wide gap capability.
2.03 ALARM HORN
A. Alarm horn shall be weatherproof, and installed in a tamperproof metal enclosure, with
alarm contacts on enclosure.
2.04 KEYPAD
A. Keypad shall be surface mounted with the following minimum features:
1. Provide full programming capability for the security system.
2. Programmable up to 96 users.
3. Provide for zone by-pass.
4. Include panic alarm initiation and silent alarm initiation.
PART 3 EXECUTION
3.01 EXAMINATION
A. Submission of a proposal confirms that the Contract Documents and site conditions are
accepted without qualifications unless exceptions are specifically noted.
B. The site shall be visited on a regular basis to appraise ongoing progress of other trades
and contracts, make allowances for all ongoing work, and coordinate the requirements of
this contract in a timely manner.
3.02 INSTALLATION
A. The System shall be installed and tested in accordance with the Manufacturer’s
Installation instructions. The following conditions are applicable:
1. Interfaces shall be coordinated with the Owner’s representative, where appropriate.
2. All necessary backboxes, pullboxes, connectors, supports, conduit, cable, and wire shall
be furnished and installed to provide a complete and reliable System installation. Exact
location of all boxes, conduit, and wiring runs shall be presented to the Owner for
approval in advance of any installation.