Specifications
St. David Catholic School Manning Architects
Gym and Classroom Replacement N10.024.00
New Orleans, Louisiana July 20, 2012
INTRUSION DETECTION SYSTEM 16650 -5
11. Communication Features - Supports telephone capture and reporting to primary and
secondary central station receivers.
12. Cross-Zoning Capability - Helps prevent false alarms by preventing a zone from
going into alarm unless its cross-zone is also faulted within five (5) minutes.
13. Pager Interface – The Control Panel shall be capable of sending event information to
an alphanumeric pager.
14. 24-Volt Power Supply – The Control Panel shall be compatible with a 24-Volt power
supply module. The module shall supply two (2) 24 vdc, rectified, unfiltered outputs,
which power:
a. Alarm notification appliances, including but not limited to sirens horns, bells and
strobes.
b. Auxiliary devices capable of operating using full-wave rectified unfiltered voltage.
15. Exit Error False Alarm Prevention Feature – The System shall be capable of
differentiating between an actual alarm and an alarm caused by leaving an entry/exit
door open. If not subsequently disarmed, the control panel shall:
a. Bypass the faulted E/E zone(s) and/or interior zones and arm the system.
b. Generate an Exit Error report by user and by zone so the central station knows
it was an exit alarm and who caused it.
16. Enhanced Walk-Test Mode – The Control Panel shall provide the installer with the
following features:
a. Automatic test of all integrated remote point module (RPM) devices, equipped
with an automatic test feature.
b. An event log shall be capable of logging the results of tested and untested zones.
c. The ability to report the result of tested and untested zones to the central station.
17. Programming - The Control shall be capable of being programmed locally or
remotely.
18. Automation Software - The Control shall be capable of interfacing with automation
software via an RS232 input on a single partition.
19. Provide status and alarm indication output to Access Control System for monitoring
by Campus Police via Access control system network. Include all interface devices,
wiring, and connections for fully functional monitoring.
2.02 ENVIRONMENTAL CONDITIONS
A. Environmental Conditions – The System shall be designed to meet the following
environmental conditions.
1. Storage Temperature – The system shall be designed for a storage temperature of -
10 C to 70C.
2. Operating Temperature - The system shall be designed for an operating temperature
of 0 C to 50C (32 F to 120F).