St. David Catholic School Manning Architects
Gym and Classroom Replacement N10.024.00
New Orleans, Louisiana July 20, 2012
INTRUSION DETECTION SYSTEM 16650 -1
SECTION 16650
INTRUSION DETECTION SYSTEM
PART 1 GENERAL
1.01 REFERENCES
A. Underwriters Laboratories (UL):
1. UL 611 – Central Station Burglar-Alarm Units
2. UL 636 – Holdup Alarm Units and Systems
3. UL 684 – Local, Central Station, and Remote Station
4. UL 1076 – Proprietary Burglar-Alarm Units and Systems
5. UL 1610 – Central-Station Burglar-Alarm Units
B. Federal Communications Commission (FCC):
1. Code of Federal Regulations Title 47 - Part 15 – Radio Frequency Devices
2. Code of Federal Regulations Title 47 - Part 68 – Connection of Terminal
Equipment to the Telephone Network
C. National Fire Protection Association (NFPA):
1. NFPA70 – National Electrical Code.
2. NFPA 72 – National Fire Protection Code
1.02 SYSTEM DESCRIPTION
A. The system shall be a Intrusion Detection system that includes the following capabilities:
1. Listed for UL Commercial Burglary.
2. Supports up to 32 zones.
3. Supports up to 150 users.
4. Supports commercial wireless devices.
5. Provides supervision of peripheral devices.
6. Supports up to 96 optional relay outputs.
7. Provides scheduling capability to allow for automated operations.
8. Supports up to eight (8) alphanumeric paging devices.
9. Supports status and alarm reporting, and conrol via Access Control System.
10. Supports alarm reporting via Internet.
11. Interfaces with automation software.
1.03 SUBMITTALS
A. Forward 6 copies of submittal data, floor plans, and riser diagrams and additional data as
required for complete description of system installation. As a minimum, submittals shall
consist of: