Specifications

St. David Catholic School Manning Architects
Gym and Classroom Replacement N10.024.00
New Orleans, Louisiana July 20, 2012
BASIC MATERIALS AND METHODS 16100 -7
(c) Masonry: Toggle bolts on hollow block and expansion bolts on solid block. Seal around
sleeves with mortar, both sides of wall.
(d) New Concrete: Concrete inserts with machine screws and bolts.
(e) Existing Concrete: Expansion bolts.
(f) Structural Steel: Spring-tension clamps.
(g) Light Steel Framing: Sheet metal screws.
(h) Fasteners for Damp, Wet, or Weather-Exposed Locations: Stainless steel.
(i) Light Steel: Sheet-metal screws.
(j) Fasteners: Select so load applied to each fastener does not exceed 25 percent of its
proof-test load.
3.08 IDENTIFICATION MATERIALS AND DEVICES
Install at locations for most convenient viewing without interference with operation and
maintenance of equipment.
Coordinate names, abbreviations, colors, and other designations used for electrical identification
with corresponding designations indicated in the Contract Documents or required by codes and
standards. Use consistent designations throughout Project.
Install continuous underground plastic markers during trench backfilling, for exterior
underground power, control, signal, and communication lines.
3.09 FIRESTOPPING
Penetrations through rated construction shall be sealed with a material capable of preventing the
passage of flames and hot gases when tested in accordance with ASTM-EB14.
1. Notify the Architect for inspection of all completed fire and/or smoke barrier walls
before any construction is installed that would conceal construction and prevent a
proper inspection. Access to random selected areas may be required by the Architect at
the time of final inspection if this notification is not given.
2. Provide detailed instructive cut sheets of the fire penetration sealing system used to the
Architect at the time of inspection. Random selective sampling by the Contractor will be
observed by the Architect and the Fire Marshal’s inspector.
3.10 MOUNTING HEIGHTS
Unless otherwise noted on the drawings or required by the Architect, the following
mounting heights shall apply. Unless noted otherwise, mounting heights are to the
centerline of the device:
1. Receptacles 18” above floor