St. David Catholic School Gym and Classroom Replacement New Orleans, Louisiana Manning Architects N10.024.00 July 20, 2012 SECTION 16010 BASIC ELECTRICAL REQUIREMENTS PART 1 - GENERAL RELATED DOCUMENTS All drawings and general provisions of the contract, including General Conditions, Supplementary Conditions, and other Division 1 Specifications, apply to this section. Separation of Specifications into Sections is for convenience only and is not intended to establish limits of work or liability.
St. David Catholic School Gym and Classroom Replacement New Orleans, Louisiana Manning Architects N10.024.00 July 20, 2012 manufacturer’s shop drawings and rough-in drawings, and adjust work accordingly to provide a coordinated installation. All adjustments and minor deviations necessary shall be made without additional cost to the owner.
St. David Catholic School Gym and Classroom Replacement New Orleans, Louisiana Manning Architects N10.024.00 July 20, 2012 Prior to submitting quotation for electrical work, Contractor shall visit and examine the job site with all authorities concerned in order to become familiar with all existing conditions pertinent to the work to be performed thereon. No additional compensation will be allowed for failure to be so informed.
St. David Catholic School Gym and Classroom Replacement New Orleans, Louisiana Manning Architects N10.024.00 July 20, 2012 the attention of the architect and engineer as an alternative product prior to the official submittal of electrical products.
St. David Catholic School Gym and Classroom Replacement New Orleans, Louisiana Manning Architects N10.024.00 July 20, 2012 all openings left in the structure for electrical work. This includes openings around conduit penetrations. EXCAVATING AND BACKFILLING The Contractor shall be responsible for all excavating and backfilling required to complete the installation of the electrical systems. All excess material and debris shall be removed. All backfilling shall be with sand.
BLANK SHEET
St. David Catholic School Gym and Classroom Replacement New Orleans, Louisiana Manning Architects N10.024.00 July 20, 2012 SECTION 16100 BASIC ELECTRICAL MATERIALS AND METHODS PART 1 – GENERAL 1.01 SUMMARY A. This Section includes the following: 1. 2. 3. 4. 5. 6. 7. Raceways. Wires, cables, and connections Wiring devices Grounding Safety Switches and fuses Supporting devices for electrical components. Equipment for utility company’s electricity metering. 1.
St. David Catholic School Gym and Classroom Replacement New Orleans, Louisiana Manning Architects N10.024.00 July 20, 2012 PART 2 - PRODUCTS 2.01 RACEWAYS EMT: Electrical metallic tubing; ANSI C80.3, zinc-coated steel. FMC: Flexible metal conduit; zinc-coated steel. IMC: Intermediate metal conduit; ANSI C80.6, zinc-coated steel, with threaded fittings. LFMC: Liquidtight flexible metal conduit; zinc-coated steel with sunlight-resistant and mineraloil-resistant plastic jacket.
St. David Catholic School Gym and Classroom Replacement New Orleans, Louisiana Manning Architects N10.024.00 July 20, 2012 All device plates shall be brushed stainless steel with matching counter sunk screws unless noted otherwise. Consult with the Architect for color selections before ordering devices. Use multigang plates where devices are grouped together. Boxes and fittings shall comply with article 314 of the NEC.
St. David Catholic School Gym and Classroom Replacement New Orleans, Louisiana Manning Architects N10.024.00 July 20, 2012 Raceway and Cable Supports: Manufactured clevis hangers, riser clamps, straps, threaded Cclamps with retainers, ceiling trapeze hangers, wall brackets, and spring-steel clamps or click-type hangers. Pipe Sleeves: ASTM A 53, Type E, Grade A, Schedule 40, galvanized steel, plain ends.
St. David Catholic School Gym and Classroom Replacement New Orleans, Louisiana Manning Architects N10.024.00 July 20, 2012 4. Below Slab on Grade or in Crawlspace: RNC. 5. Connection to Vibrating Equipment: FMC; except in wet or damp locations: LFMC. 6. Boxes and Enclosures: NEMA 250, Type 1, unless otherwise indicated. 3.03 RACEWAY AND CABLE INSTALLATION Conceal raceways and cables, unless otherwise indicated, within finished walls, ceilings, and floors.
St. David Catholic School Gym and Classroom Replacement New Orleans, Louisiana Manning Architects N10.024.00 July 20, 2012 Remote-Control Signaling and Power-Limited Circuits, Classes 1, 2, and 3: Insulated conductors in raceway unless otherwise indicated. Not Allowed: Type MC or NM for branch circuits. 3.05 WIRING INSTALLATION Make splices and taps that are compatible with conductor material and that possess equivalent or better mechanical strength and insulation ratings than unspliced conductors.
St. David Catholic School Gym and Classroom Replacement New Orleans, Louisiana Manning Architects N10.024.00 July 20, 2012 (c) Masonry: Toggle bolts on hollow block and expansion bolts on solid block. Seal around sleeves with mortar, both sides of wall. (d) New Concrete: Concrete inserts with machine screws and bolts. (e) Existing Concrete: Expansion bolts. (f) Structural Steel: Spring-tension clamps. (g) Light Steel Framing: Sheet metal screws.
St. David Catholic School Gym and Classroom Replacement New Orleans, Louisiana 2. 3. 4. 5. 6. Manning Architects N10.024.00 July 20, 2012 Toggle Switches 48” above floor Panelboards 72” to top Telephone Outlets 18” above floor Data Outlets 18” above floor Meter Can 60”-72” to centerline Mounting heights may be adjusted in masonry applications to simplify installation where approved by the Architect.
St. David Catholic School Gym and Classroom Replacement New Orleans, Louisiana Manning Architects N10.024.00 July 20, 2012 SECTION 16400 PANELBOARDS PART 1 – GENERAL SUMMARY This Section includes distribution and branch-circuit panelboards. SUBMITTALS Product Data: For each type of panelboard, overcurrent protective device, accessory, and component indicated. Include dimensions and manufacturers' technical data on features, performance, electrical characteristics, ratings, and finishes.
St. David Catholic School Gym and Classroom Replacement New Orleans, Louisiana Manning Architects N10.024.00 July 20, 2012 PART 2 – PRODUCTS MANUFACTURERS Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following: (a) (b) (c) (d) Eaton Corp.; Cutler-Hammer Products. Siemens Energy & Automation, Inc. Square D Co.
St. David Catholic School Gym and Classroom Replacement New Orleans, Louisiana Manning Architects N10.024.00 July 20, 2012 LIGHTING AND APPLIANCE BRANCH-CIRCUIT PANELBOARDS Branch Overcurrent Protective Devices: Bolt-on circuit breakers, replaceable without disturbing adjacent units. Doors: Front mounted with concealed hinges; secured with flush latch with tumbler lock; keyed alike. DISTRIBUTION PANELBOARDS Doors: Front mounted, and secured with vault-type latch with tumbler lock; keyed alike.
St. David Catholic School Gym and Classroom Replacement New Orleans, Louisiana Manning Architects N10.024.00 July 20, 2012 208Y/120V Distribution: 400V 400V 400V 480Y/277V Distribution: 800V 800V 800V 9. SPD shall have a minimum EMI/RFI filtering of up to –30 dB over the range of 100 kHz to 100 MHz. 10. SPD shall be provided with one set of NO/NC dry contacts. 11.
St. David Catholic School Gym and Classroom Replacement New Orleans, Louisiana Manning Architects N10.024.00 July 20, 2012 IDENTIFICATION Identify field-installed conductors, interconnecting wiring, and components; provide warning signs as specified in Division 16 Section "Basic Electrical Materials and Methods." Panelboard Nameplates: Label each panelboard with engraved metal or laminated-plastic nameplate mounted with corrosion-resistant screws.
BLANK SHEET
St. David Catholic School Gym and Classroom Replacement New Orleans, Louisiana Manning Architects N10.024.00 July 20, 2012 SECTION 16500 LIGHTING FIXTURES PART 1 - GENERAL 1.01 SUMMARY A. This Section includes the following: 1. Lighting fixtures with lamps and ballasts. 2. Emergency lighting units. 3. Exit signs. 4. Accessories, including fluorescent fixture dimmers, occupancy sensors, etc. B. All existing lighting fixtures within each building are presumed to be functional.
St. David Catholic School Gym and Classroom Replacement New Orleans, Louisiana Manning Architects N10.024.00 July 20, 2012 D. NFPA 101 Compliance: Comply with visibility and luminance requirements for exit signs. PART 2 – PRODUCTS A. All light fixtures shall be as specified on the drawings. B. Fixtures to be installed in damp or wet locations shall be listed by Underwriters' Laboratory for that purpose. C.
St. David Catholic School Gym and Classroom Replacement New Orleans, Louisiana Manning Architects N10.024.00 July 20, 2012 PART 3 – EXECUTION A. Light fixtures shall be set level, plumb, and square with ceilings and walls. B. Light fixtures in or on Grid-Type Suspended Ceilings shall be supported independently of the ceiling. C. Fixtures to be installed in or on painted ceilings and/or walls shall not be installed until painting is completed.
BLANK SHEET
St. David Catholic School Gym and Classroom Replacement New Orleans, Louisiana Manning Architects N10.024.00 July 20, 2012 SECTION 16600 FIRE DETECTION SYSTEM PART 1 - GENERAL 1.01 DESCRIPTION A. This section of the specifications includes the furnishing and installing, of a complete and operational Fire Alarm System. The system shall be analog, addressable, with voice evacuation. B.
St. David Catholic School Gym and Classroom Replacement New Orleans, Louisiana Manning Architects N10.024.00 July 20, 2012 7. System shall interact with the Access Control system. Through an interface with the Access Control system, the Access Control system shall unlock all exterior doors, permitting entry by fire department or first responding personnel upon initiation of general alarm. 1.03 QUALITY ASSURANCE A.
St. David Catholic School Gym and Classroom Replacement New Orleans, Louisiana Manning Architects N10.024.00 July 20, 2012 D. Contractor shall provide all documents required by the State Fire Marshal to review. Documents shall include all calculations and data necessary. These documents shall be sent to the Architect for his forwarding to the State Fire Marshal. This Contractor shall pay all fees associated with the Fire Marshal submittal.
St. David Catholic School Gym and Classroom Replacement New Orleans, Louisiana Manning Architects N10.024.00 July 20, 2012 PART 2 - PRODUCTS 2.01 EQUIPMENT AND MATERIAL, GENERAL A. All equipment and components shall be new and the manufacturer's current model. The materials, appliances, equipment, and devices shall be tested and listed by a nationally recognized approvals agency for use as part of a protective signaling system, meeting the National Fire Alarm Code. B.
St. David Catholic School Gym and Classroom Replacement New Orleans, Louisiana Manning Architects N10.024.00 July 20, 2012 4. Wiring used for the multiplex communication loop shall be twisted and shielded. The system shall permit use of IDC and IAC wiring in the same conduit with the communication loop. 5. All field wiring shall be supervised for open circuits, short circuits, and ground faults. C.
St. David Catholic School Gym and Classroom Replacement New Orleans, Louisiana Manning Architects N10.024.00 July 20, 2012 5. Editing of the program shall not interfere with the normal operation of the control panel. If a fire condition is detected during a programming operation, the system shall exit programming and perform fire protection functions as programmed. 6. A special program check function shall be provided to detect common operator errors. 7.
St. David Catholic School Gym and Classroom Replacement New Orleans, Louisiana Manning Architects N10.024.00 July 20, 2012 2. Speakers shall include field selectable power taps from 1/8 watt to 8 watts with listed sound output up to 96 dBA for speakers and 93 dBA for speaker strobes. All models shall have provisions for standard reverse polarity type supervision for strobe portion and IN/OUT field wiring using terminals that accept #12 to #18 AWG wiring.
St. David Catholic School Gym and Classroom Replacement New Orleans, Louisiana Manning Architects N10.024.00 July 20, 2012 2. All operated stations shall have a positive, visual indication of operation and utilize a key type reset. 3. Manual stations shall be constructed of LEXAN with clearly visible operating instructions provided on the cover. The word FIRE shall appear on the front of the stations in raised letters, 1.75 inches or larger. 4.
St. David Catholic School Gym and Classroom Replacement New Orleans, Louisiana Manning Architects N10.024.00 July 20, 2012 3. The isolator module shall not require any address-setting, and its operations shall be totally automatic. It shall not be necessary to replace or reset an isolator module after its normal operation. 4. The isolator module shall mount in a standard 4-inch deep electrical box or in a surface mounted backbox.
St. David Catholic School Gym and Classroom Replacement New Orleans, Louisiana Manning Architects N10.024.00 July 20, 2012 5. 6. 7. 8. 9. Open and short signaling line circuits and verify that the trouble signal activates. Open and short indicating appliance circuits and verify that trouble signal activates. Ground all circuits and verify response of trouble signals. Check presence and audibility of tones at all alarm indicating devices.
St. David Catholic School Gym and Classroom Replacement New Orleans, Louisiana Manning Architects N10.024.00 July 20, 2012 SECTION 16650 INTRUSION DETECTION SYSTEM PART 1 GENERAL 1.01 REFERENCES A. Underwriters Laboratories (UL): 1. 2. 3. 4. 5. UL 611 – Central Station Burglar-Alarm Units UL 636 – Holdup Alarm Units and Systems UL 684 – Local, Central Station, and Remote Station UL 1076 – Proprietary Burglar-Alarm Units and Systems UL 1610 – Central-Station Burglar-Alarm Units B.
St. David Catholic School Gym and Classroom Replacement New Orleans, Louisiana 1. 2. 3. 4. 5. 6. 7. Manning Architects N10.024.
St. David Catholic School Gym and Classroom Replacement New Orleans, Louisiana Manning Architects N10.024.00 July 20, 2012 1. Basic Hardwired Zones - The control shall provide eight (8) style-B hardwire zones with the following characteristics: a. EOLR supervision (optional for zones 3-8): Shall support N.O. or N.C. sensors (EOLR supervision required for UL installations). b. Zones/Points shall be individually assignable to one of eight (8) partitions. c.
St. David Catholic School Gym and Classroom Replacement New Orleans, Louisiana Manning Architects N10.024.00 July 20, 2012 c. Providing four programmable single-button function keys, which can be used for: 1. Panic Functions –activated by wired and wireless keypads; reported separately by partition. 2. Keypad Macros –32 keypad macro commands per system (each macro is a series of keypad commands). Assignable to the A, B, C, and D keys by partition. 6.
St. David Catholic School Gym and Classroom Replacement New Orleans, Louisiana Manning Architects N10.024.00 July 20, 2012 11. Communication Features - Supports telephone capture and reporting to primary and secondary central station receivers. 12. Cross-Zoning Capability - Helps prevent false alarms by preventing a zone from going into alarm unless its cross-zone is also faulted within five (5) minutes. 13.
St. David Catholic School Gym and Classroom Replacement New Orleans, Louisiana Manning Architects N10.024.00 July 20, 2012 3. Humidity - The system shall be designed for normal operation in an 85% relative humidity environment. 4. Electromagnetic Interference – The system shall meet or exceed the requirements of FCC Part 15, Class B devices, FCC Part 68, IEC EMC directive. 2.03 MOTION DETECTOR A.
St. David Catholic School Gym and Classroom Replacement New Orleans, Louisiana Manning Architects N10.024.00 July 20, 2012 3. All wiring shall be installed in minimum ½” conduit, cable, installed parallel and square with building lines. Conduit fill shall not exceed forty percent (40%). All wires shall be gathered and tied up to create an orderly installation. 3.03 TESTING AND CERTIFICATION A.
BLANK SHEET
St. David Catholic School Gym and Classroom Replacement New Orleans, Louisiana Manning Architects N10.024.00 July 20, 2012 SECTION 16670 ACCESS CONTROL SYSTEM PART 1 - GENERAL 1.1 SUMMARY A. Furnish all labor, materials, equipment, and service necessary for a complete and operating Access Control and Monitoring System (ACMS) as shown on the drawings and as described herein. Drawings are diagrammatic only. B.
St. David Catholic School Gym and Classroom Replacement New Orleans, Louisiana Manning Architects N10.024.00 July 20, 2012 configuration software shall be required for system programming or initial setup. ACMS systems that require proprietary configuration software are not acceptable. E. The contractor shall provide the appropriate quantity of legal copies of all software tools, configuration tools, management tools, and utilities used during system commissioning and installation.
St. David Catholic School Gym and Classroom Replacement New Orleans, Louisiana WBI LAN WAN PICS .CSV .PDF Manning Architects N10.024.00 July 20, 2012 Web Browser Interface Local Area Network Wide Area Network Product Interoperability Compliance Statement Comma Separated Value file format Portable Data File format 1.5 DIVISION OF WORK A.
St. David Catholic School Gym and Classroom Replacement New Orleans, Louisiana Manning Architects N10.024.00 July 20, 2012 configuration and programming that is generated for a given project and /or configured for use within Niagara AX Framework (Niagara) based controllers and/or servers and any related LAN / WAN / Intranet and all connected routers and devices. 1.7 DELIVERY, STORAGE AND HANDLING A. Provide factory-shipping cartons for each piece of equipment and control device.
St. David Catholic School Gym and Classroom Replacement New Orleans, Louisiana Manning Architects N10.024.00 July 20, 2012 B. The Security Controller shall provide the following hardware features as a minimum: 1. 2. 3. 4. 5. 6. 7. 8. 9. 10.
St. David Catholic School Gym and Classroom Replacement New Orleans, Louisiana Manning Architects N10.024.00 July 20, 2012 6. Intrusion Zones. The function allows set-up of a defined area for monitoring and alarming by allowing multiple sensing points to be combined into a logical group. Intrusion zones shall be armed or disarmed using a schedule, badge reader, keypad, badge reader/keypad combination, or manual override. 7. Tenant Segregation.
St. David Catholic School Gym and Classroom Replacement New Orleans, Louisiana Manning Architects N10.024.00 July 20, 2012 number to initiate a duress alarm. The location shall appear to access normally, but an alarm shall be generated to notify the system operators that an access occurred under duress. 14. Schedules.
St. David Catholic School Gym and Classroom Replacement New Orleans, Louisiana Manning Architects N10.024.00 July 20, 2012 d. Off / Disabled 4. Alarm generation shall be selectable for annunciation type and acknowledgement requirements: a. Enable/Disable Alarm indicator b. Require Notes on Alarm Acknowledgement 5. Alarms shall display the following states: a. b. c. d.
St. David Catholic School Gym and Classroom Replacement New Orleans, Louisiana Manning Architects N10.024.00 July 20, 2012 1. Screen message text at central monitoring point on campus network 2. Email of the complete alarm message to multiple recipients via the owner’s e-mail service. Provide the ability to route and email alarms based on: a. Day of week b. Time of day c. Recipient 3. Pagers via paging services that initiate a page on receipt of email message via the owner’s e-mail service 4.
St. David Catholic School Gym and Classroom Replacement New Orleans, Louisiana Manning Architects N10.024.00 July 20, 2012 B. Copies of the current database and the most recently saved database shall be stored in the Security Controller. The age of the most recently saved database is dependent on the userdefined database save interval. 2.6 OTHER ACCESS CONTROL SYSTEM HARDWARE A. Proximity Card readers 1.
St. David Catholic School Gym and Classroom Replacement New Orleans, Louisiana Manning Architects N10.024.00 July 20, 2012 c. Securitron 2. Recessed as specified for each location 3. SPDT contact configuration 4. Operate over normal door opening tolerances F. Power Supplies / Battery Chargers 1. Manufacturers: Subject to compliance with requirements, provide products by one of the manufacturers specified. a. Altronix b. Honeywell c. Schlage d. Securitron 2. 3. 4. 5. 6. 7.
St. David Catholic School Gym and Classroom Replacement New Orleans, Louisiana Manning Architects N10.024.00 July 20, 2012 a. Honeywell b. PowerSonic 2. Shall be housed in a sealed impact-resistant case 3. Shall be securely mounted in an enclosure 4. Shall be sized to provide 8 hours backup at specified voltage and 120% rated current draw to all connected devices. PART 3 - EXECUTION 3.1 INSTALLATION A.
St. David Catholic School Gym and Classroom Replacement New Orleans, Louisiana Manning Architects N10.024.00 July 20, 2012 3.4 WARRANTY ACCESS A. The Owner shall grant to this contractor, reasonable access to the ACMS during the warranty period. B. The owner shall allow the contractor to access the ACMS and FMCS from a remote location for the purpose of diagnostics and troubleshooting, via the Internet, during the warranty period. 3.5 ACCEPTANCE TESTING A.
St. David Catholic School Gym and Classroom Replacement New Orleans, Louisiana Manning Architects N10.024.00 July 20, 2012 to training so that the owners' personnel can start to familiarize themselves with the system before classroom instruction begins. 2. First Follow-Up Training: 1/2 day (4 hours total) approximately two weeks after initial training, and before Formal Acceptance. These sessions will deal with more advanced topics and answer questions. 3.
St. David Catholic School Gym and Classroom Replacement New Orleans, Louisiana Manning Architects N10.024.00 July 20, 2012 SECTION 16750 PA/INTERCOM SYSTEM PART 1 – GENERAL 1.2 GENERAL REQUIREMENTS A. The Contractor shall furnish and install all equipment including, but not limited to, outlet boxes, conduit (with pull strings), wiring, telephones, annunciators, speakers, and microphones as shown on the plans, and all other equipment necessary to provide a complete and operating system. B.
St. David Catholic School Gym and Classroom Replacement New Orleans, Louisiana Manning Architects N10.024.00 July 20, 2012 B. The Contractor shall maintain at his facility the necessary spare parts in the proper proportion as recommended by the equipment manufacturer to maintain and service the equipment being supplied. This facility shall be available for inspection by the engineer. C. The supplying Contractor shall have attended the manufacturer's installation and service school. D.
St. David Catholic School Gym and Classroom Replacement New Orleans, Louisiana Manning Architects N10.024.00 July 20, 2012 2.5 The system shall be provided with four (4) multifunction ports for connection of administrative phones, any loop start trunk (LST) port of a KEY or PBX telephone system. All communication between administrative phones shall be non-blocking. Provide a minimum of one LST port interface as part of this basic specification. 2.
St. David Catholic School Gym and Classroom Replacement New Orleans, Louisiana Manning Architects N10.024.00 July 20, 2012 2.15.4 AM/FM CD Combination Player 2.16 Seventy-Two (72) paging zones and a dial on the fly group with two (2) priority levels of all call capability. Paging into any one zone shall not interrupt any program(s) previously distributed.
St. David Catholic School Gym and Classroom Replacement New Orleans, Louisiana Manning Architects N10.024.00 July 20, 2012 2.25.2 Speaker and microphone for hands free communication. Administrative phones requiring a push to talk switch shall not be accepted. 2.25.3 Multiple touch programmable function buttons for frequently dialed functions, page groups, bell schedules, program distribution, etc. 2.25.4 Emergency programmable buttons for alert and evacuation tones. 2.25.5 Mute function for privacy. 2.25.
St. David Catholic School Gym and Classroom Replacement New Orleans, Louisiana Manning Architects N10.024.00 July 20, 2012 1.3” (3.3 cm) D and the unit shall weigh .55 lb. (.25 kg). 2.30 The hallway and other multi speaker areas shall use speakers with an 8” dual cone design with a minimum frequency response of 30Hz-18kHz. It shall have a minimum voice coil diameter of ¾” and be capable of handling 10 watts of program power.
St. David Catholic School Gym and Classroom Replacement New Orleans, Louisiana 2.42 Manning Architects N10.024.00 July 20, 2012 Gymnasium Sound System A. Speakers: Octasound SP820A, omni-directional, 200W RMS, 400W peak, or approved equal. B. Speaker Jacks: STX chassis connectors, metal body, soldered connection. C. Speaker Cable: STX cable connectors, metal body, #12 AWG stranded copper hard usage cable, minimum 12 feet. Provide 2 sets, 1 primary for left and right cahnnels, and 1 spare set. D.
St. David Catholic School Gym and Classroom Replacement New Orleans, Louisiana Manning Architects N10.024.00 July 20, 2012 3.2.1 Check out of the installation shall be made by the contractor. The system shall be free of short circuits, ground loops, parasitic oscillations, excessive system noise and hum, and instability. The Contractor shall, at his own expense, make any changes required to meet these performance requirements. 3.2.
St. David Catholic School Gym and Classroom Replacement New Orleans, Louisiana Manning Architects N10.024.00 July 20, 2012 SECTION 16760 VIDEO SURVEILLANCE PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section. 1.2 SUMMARY A.
St. David Catholic School Gym and Classroom Replacement New Orleans, Louisiana Manning Architects N10.024.00 July 20, 2012 B. Shop Drawings: Detail assemblies of standard components that are custom assembled for specific application on this Project. 1. Functional Block Diagram: Show single-line interconnections between components for signal transmission and control. Show cable types and sizes. 2. Dimensioned plan and elevations of equipment racks, control panels, and consoles.
St. David Catholic School Gym and Classroom Replacement New Orleans, Louisiana Manning Architects N10.024.00 July 20, 2012 2. Interior, Controlled Environment: System components, except central-station control unit, installed in air-conditioned interior environments shall be rated for continuous operation in ambient temperatures of 36 to 122 deg F dry bulb and 20 to 90 percent relative humidity, noncondensing. NEMA 250, Type 1 enclosures. 3.
St. David Catholic School Gym and Classroom Replacement New Orleans, Louisiana Manning Architects N10.024.00 July 20, 2012 2.3 POWER SUPPLIES A. Power Supplies: Low-voltage power supplies matched for voltage and current requirements of cameras and accessories, type as recommended by camera and lens manufacturer. Provide minimum one power supply per DVR location. 1. Enclosure: NEMA 250, Type 1 indoors, NEMA 250, Type 4X outdoors. 2.4 CAMERA-SUPPORTING EQUIPMENT A.
St. David Catholic School Gym and Classroom Replacement New Orleans, Louisiana Manning Architects N10.024.00 July 20, 2012 1. Built in DVD/CD R/W +/-. 2. Support the addition of up to 14 external USB HDD’s, 6 SCSI-2 HDD’s where each drive can be up to 2TB each and a USB Jump Drive. 3. Cascade Capability: Connection of up to 16 DX-TL5000U with keyboard access via to display any video to a master monitor. 4. Include setup wizard to simplify setup and programming. B. Operations: 1.
St. David Catholic School Gym and Classroom Replacement New Orleans, Louisiana Manning Architects N10.024.00 July 20, 2012 1. Capability to archive to external HDD or DVD. Provide external HDD storage capacity as required for 72 hours worth of images from 16 cameras per DVR, at a record rate of 1 PPS per camera. G. Search Options: 1. 2. 3. 4. Time and date alarm number bookmark motion search. H. Copy: 1. 2. 3. 4. Capability to copy images to a HDD connected to USB ports or NAS port.
St. David Catholic School Gym and Classroom Replacement New Orleans, Louisiana 10. 11. 12. 13. 14. 15. Manning Architects N10.024.00 July 20, 2012 e. Record mode is activated f. HD data storage has reached a specified percent of capacity. Independent or global alarm recording per alarm trigger. Alarm contact (Mode Out 1-4) shall have individual programmable polarity that can trigger telemetry preset. Capability to record multiple cameras per alarm trigger.
St. David Catholic School Gym and Classroom Replacement New Orleans, Louisiana 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. Manning Architects N10.024.00 July 20, 2012 Support viewing covert cameras over the network by authorized personnel. Provide access to the units event list and its associated video when alarms are recorded. Support storing of digital images to a PC HDD, DVD/CD and USB Memory drive. Playback images copied from DVR to DVD/CD or USB Memory drives.
St. David Catholic School Gym and Classroom Replacement New Orleans, Louisiana Manning Architects N10.024.00 July 20, 2012 D. Splices, Taps, and Terminations: For power and control wiring, in junction, pull, and outlet boxes; terminal cabinets; and equipment enclosures. Tighten electrical connectors and terminals according to manufacturer's published torque-tightening values. If manufacturer's torque values are not indicated, use those specified in UL 486A and UL 486B.
St. David Catholic School Gym and Classroom Replacement New Orleans, Louisiana Manning Architects N10.024.00 July 20, 2012 2. Verify operation of auto-iris lenses. Set back-focus of fixed focal length lenses. At focus set to infinity, simulate nighttime lighting conditions by using a dark glass filter of a density that produces a clear image. Adjust until image is in focus with and without the filter. 3. Set back-focus of zoom lenses.
St. David Catholic School Gym and Classroom Replacement New Orleans, Louisiana Manning Architects N10.024.00 July 20, 2012 A. Clean installed items using methods and materials recommended in writing by manufacturer. B. Clean video surveillance system components, including camera-housing windows, lenses, and monitor screens. 3.6 DEMONSTRATION A. Engage a factory-authorized service representative to train Owner's maintenance personnel to adjust, operate, and maintain video surveillance equipment. 1.