Specifications
3. INSTALLATION
3.1 General Specification
I-3
3. INSTALLATION
3.1 General Specification
Unit name Remote I/O unit
Type name FCU6-DX561
During
operation
0 to 55°C * Note
Ambient
temperature
During
storage
–20 to 60°C
During
operation
45 to 75% RH (with no dew condensation)
Ambient
humidity
During
storage
45 to 80% RH (with no dew condensation)
Vibration resistance 4.9m/s
2
or less (during operation)
Shock resistance
29.4m/s
2
or less (during operation)
98m/s
2
or less (during transportation)
Working atmosphere No corrosive gases, or high levels of dust or oil mist
Power noise 1kVA (P-P)
Withstand voltage
500VAC for one minute
Across entire output terminal batch and grounding terminal
Insulation resistance
5MΩ or more with 500VDC megger tester
Across entire output terminal batch and grounding terminal
General specifications
Grounding
Class D grounding
Use without grounding is possible if grounding is not possible.
Power voltage
24VDC +10%/−15%
(Must be insulated from 100VAC and 200VAC power supply)
Instantaneous stop
tolerance time
Operation continues when power instantaneously stops
for 4ms or less.
Power fuse
Chip type fuse incorporated
(SSTC 0.8A Maker: SOC UL198G approved, CSA C22.2 No. 59.2)
Power consumption Approx. 10W (Only control section; excludes input/output section)
Rush current Approx. 20A/1ms, approx. 5A/10ms
Sensor power None
Weight 1.8kg
Power specifications
Unit size Refer to Appendix.
* Note If the ambient temperature is 55°C or more, lower to 55°C or less with forced cooling.