<Error log> (continued)
LOG number
LOG display
example in the
client software
Cause Remedy
Call-out
signal
output
Alert
level*1
5200 LOG5200 • The recorder is used in a high
temperature environment.
• Turn off the power and install the
recorder in an environment of 5 to 40
°C.
Output Minor
5201 LOG5201 • The recorder is used in a high
temperature environment.
• Contact your dealer. Output Major
5300 LOG5300 • The fan stops. • If the fan stops, turn off the power
and contact your dealer immediately.
Output Major
8000 LOG8000 • An error occurs in LAN LINK. • Check the LAN connection. Does not
output
Minor
8501 LOG8501 • Recording stops temporarily because the
received data size becomes too large.
- Does not
output
Minor
<Operation log>
LOG number
LOG display
example in the
client software
Operation
0001 P-LOSS Power failure occurs during operation.
0002 P-RETURN Power failure is recovered.
0110 REC OFF Normal recording stops.
0111 REC ON Normal recording starts.
0112 REC COM OFF Normal recording stops via communucation.
0113 REC COM ON Normal recording starts via communucation.
0501 SYS RST RESET button on the rear panel is pressed.
0590 WNG RESET The call-out output is stopped.
0900 FW VER.UP Main fi rmware is updated.