Instruction manual
PARAMETER DEFINITIONS
24
5.10 A500(L) PARAMETERS
5.10.1 Normal Parameter Area
You can use the Register to make parameter settings from the network.
The last three digits of Register are the parameter number.
Standard parameter examples are introduced below. Refer to the
examples and make parameter settings.
For the parameter data and details, refer to the inverter and option
manuals.
Pr Reg Definition
Range
Factory
setting
Decimal
Hex
Pr. 0 41000 Torque Boost 0-30 0-12C
6% / 4% /
3% / 2%
Pr. 1 41001 Maximum frequency 0-120 0-2EE0 120Hz
Pr. 2 41002 Minimum frequency 0-120 0-2EE0 0Hz
Pr. 3 41003 Base frequency 0-400 0-9C40 60Hz
Pr. 4 41004 Multi-speed setting (high speed) 0-400 0-9C40 60Hz
Pr. 5 41005 Multi-speed setting (middle speed) 0-400 0-9C40 30Hz
Pr. 6 41006 Multi-speed setting (low speed) 0-400 0-9C40 10Hz
…
…
…
…
…
…
REMARKS
1. Pr. 77 (41077) is Read-Only from MBP, it cannot be written from network.
2. Pr. 79 (41079) is Read-Only from MBP, it cannot be written from network.
Pr. 79 = 6 is switch over mode.