Instruction manual
PARAMETER DEFINITIONS
21
*1 Bit-Map for Register 40215
Input Terminal Monitor:
*2 Bit-Map for Register 40216
Outp Terminal Monitor:
The bit-wise data here reflect Pr. 190 to 195; if assignments for terminals are
changed, the bit-map may not be the same.
40215 RTM15 Inp Termnl Status
(*1) ——
40216 RTM16 Outp Termnl Status
(*2) ——
40217 RTM17 Load Meter 0.1% 0.1%
40218 RTM18 Motor Excitatn I 0.01A 0.1A
40219 RTM19 Positive Pulse — —
40220 RTM20 Cumulative Energ t 1h 1h
40222 RTM22 Orientatn Status — —
40223 RTM23 Actl Op t 1h 1h
40224 RTM24 Motor Load Factr 0.1% 0.1%
40225 RTM25 Cumulative Powr 1kWh 1kWh
15..12 11 10 9 8 7 6
0 CS RES STOP MRS JOG RH
543210
RM RL RT AU STR STF
15..6543210
0 Relay FU OL IPF SU RUN
REMARKS
Modbus Plus is a single command machine. Only one command can be sent to
the FR-A5NM at a single time. Multiple commands to a single slave is NOT
supported. Please send one command for each terminal assignment.
Register Definition
Minimum Setting
Increments
(A500, F500)
Minimum Setting
Increments
(A500L, F500L)