PARAMETER DEFINITIONS
20
5.4 Using the Modsoft MSTR Block
The MSTR control register usage is as follows:
5.5 Real-Time Monitor
PLC
Register
Register
Value
Value Base Description
n 1,2 decimal
Commands MSTR function:
1 = write; 2 = read
n+1 xxxx hexadecimal MSTR function error code
n+2 1 decimal
Number of registers to be written/read
to /from the inverter
n+3 rrrr decimal
Specifies the inverter register to write/
read to/from. Value represents an
offset starting w/register 40000
(i.e. 1 = 40001; 49 = 40049).
n+4, 5, 6, 7 node number decimal
Routing registers contain Modbus Plus
nodes for communication routing. The
first register following the register
containing the inverter node number
must contain a 1 value. Remaining
routing registers must contain a 0
value.
Register Definition
Minimum Setting
Increments
(A500, F500)
Minimum Setting
Increments
(A500L, F500L)
40201 RTM01 Outp f 0.01Hz 0.01Hz
40202 RTM02 Outp I 0.01A 0.1A
40203 RTM03 Outp V 0.1V 0.1V
40205 RTM05 f Sett Val 0.01Hz 0.01Hz
40206 RTM06 Runng Spd 1r/min 1r/min
40207 RTM07 Motor Torq 0.1% 0.1%
40208 RTM08 Convrtr Outp V 0.1V 0.1V
40209 RTM09 Regen Brake Duty 0.1% 0.1%
40210
RTM10 Electr Overcur Protectn
Load Factr
0.1% 0.1%
40211 RTM11 Outp I Peak 0.01A 0.1A
40212 RTM12 Converter Peak Outp V 0.1V 0.1V
40213 RTM13 Inverter Input Powr 0.01kW 0.1kW
40214 RTM14 Inverter Output Powr 0.01kW 0.1kW