PARAMETER DEFINITIONS
19
5.3 System Environment Variable (SEV) Interface
*1 Regarding access
WO........Only writing is enabled (reading is disabled)
RO.........Only reading is enabled (writing is disabled)
R/W .......Both reading and writing are enabled
*2 Writing any value to the parameter 40002 resets the inverter.
*3 Communication parameter (Pr. 117 to Pr. 124, Pr. 331 to Pr. 342) are not
cleared.
*4 For read values of inverter status and write values of control input command,
refer to page 17, 18.
*5 For read values of operation mode and inverter setting, refer to the table below.
Programmed operation mode is displayed only for the FR- A500(L) series.
*6 Writing to Register 40014 or 40015 can be read out from Register 40014.
*7 For read values of inverter status 2, refer to page 18.
Inverter Reg Definition Access
(*1)
WriteVal
40001 UsrClrValSett WO 0000h
40002 Inverter Reset (*2) WO XXXXh
40003 PrClr WO 965Ah
40004 PrAllClr WO 99AAh
40005 PrUsrClr WO 5A55h
40006 PrClr (*3) WO 5A96h
40007 PrAllClr (*3) WO AA99h
40008 PrUsrClr (*3) WO 555Ah
40009 Inverter Status 1/CtrlInpCmd (*4) R/W
00XXh/
0XXXh
40010 OpMode / Inverter Config R/W (*5)
40013 f Sett Val R/W ffggh
40014 Runng f (RAM) (*6) R/W ffggh
40015
Runng f (E
2
PROM) (*6)
WO ffggh
40019 Inverter Status 2 (*7) RO —
Operation Mode Read Value Write Value
External operation mode 0000h 0010h
PU operation mode 0001h 0011h
External jog mode 0002h —
PU jog mode 0003h —
Net mode 0004h 0014h
Combined mode 0005h —
Programmed operation mode 0006h —