Instruction manual

PARAMETER DEFINITIONS
19
5.3 System Environment Variable (SEV) Interface
*1 Regarding access
WO........Only writing is enabled (reading is disabled)
RO.........Only reading is enabled (writing is disabled)
R/W .......Both reading and writing are enabled
*2 Writing any value to the parameter 40002 resets the inverter.
*3 Communication parameter (Pr. 117 to Pr. 124, Pr. 331 to Pr. 342) are not
cleared.
*4 For read values of inverter status and write values of control input command,
refer to page 17, 18.
*5 For read values of operation mode and inverter setting, refer to the table below.
Programmed operation mode is displayed only for the FR- A500(L) series.
*6 Writing to Register 40014 or 40015 can be read out from Register 40014.
*7 For read values of inverter status 2, refer to page 18.
Inverter Reg Definition Access
(*1)
WriteVal
40001 UsrClrValSett WO 0000h
40002 Inverter Reset (*2) WO XXXXh
40003 PrClr WO 965Ah
40004 PrAllClr WO 99AAh
40005 PrUsrClr WO 5A55h
40006 PrClr (*3) WO 5A96h
40007 PrAllClr (*3) WO AA99h
40008 PrUsrClr (*3) WO 555Ah
40009 Inverter Status 1/CtrlInpCmd (*4) R/W
00XXh/
0XXXh
40010 OpMode / Inverter Config R/W (*5)
40013 f Sett Val R/W ffggh
40014 Runng f (RAM) (*6) R/W ffggh
40015
Runng f (E
2
PROM) (*6)
WO ffggh
40019 Inverter Status 2 (*7) RO
Operation Mode Read Value Write Value
External operation mode 0000h 0010h
PU operation mode 0001h 0011h
External jog mode 0002h
PU jog mode 0003h
Net mode 0004h 0014h
Combined mode 0005h
Programmed operation mode 0006h