TRANSISTORIZED INVERTER -INSTRUCTION MANUAL- Modbus Plus COMMUNICATION OPTION FR-A5NM
Thank you for choosing the Mitsubishi transistorized inverter option unit. This instruction manual gives handling information and precautions for use of this equipment. Incorrect handling might cause an unexpected fault. Before using the equipment, please read this manual carefully to use the equipment to its optimum.
2. Injury Prevention CAUTION • Apply only the voltage specified in the instruction manual to each terminal to prevent burst, damage, etc. • Ensure that the cables are connected to the correct terminals. Otherwise, burst, damage, etc. may occur. • Always make sure that polarity is correct to prevent burst, damage, etc. • While power is on or for some time after power-off, do not touch the inverter as it is hot and you may get burnt. 3.
CONTENTS 1. INTRODUCTION 1.1 1.2 General ............................................................................................. 1 Structure ........................................................................................... 2 2. INSTALLATION 2.1 2.2 2.3 4 Pre-Installation Checks..................................................................... 4 Node address setting........................................................................ 7 Communication cable ...........................
1. INTRODUCTION 1.1 General Thank you for choosing this option unit for the Mitsubishi FR-A500(L)/ F500(L) series transistorized inverters. Please read this manual carefully before using this option unit. This instruction manual gives handling information and precautions for use of this product as well as the information required for the transmission of data to and from the inverter via a Modbus Plus network.
INTRODUCTION 1.
INTRODUCTION Diagnostic LED Status Indicator The green LED located next to the address DIP switch on the Modbus Plus option top board provides indication of communication status. The LED on the bottom board will be solid green if the option CPU acts correctly. The following describes the LED on the top board definitions. Green Flash every 160ms Flash every 1s 2 flashes, off 2s 3 flashes, off 1.7s 4 flashes, off 1.4s State of system Node is working normally.
2. INSTALLATION Remove the drive cover following the inverter instruction manual and install the option unit using the following procedure: 2.1 Pre-Installation Checks (1) Check the inverter type. You may use the option unit only with a FR-A500(L)/F500(L) series inverter. You must not use it with any other series (e.g. A200E, A200, A100, Z and F series).
INSTALLATION (5) Secure the option unit to the inverter with two mounting screws. If the screw holes in the option unit do not line up with the inverter mounting holes, check that the connectors have been fitted correctly. (6) To ensure proper Network Grounding, connect a harness (NOT Supplied) from FR-A5NM Ground terminal to inverter Ground terminal. For ease of routing, the harness should be passed between the Top and Bottom board. (Refer to the following diagram.) Recommended crimping terminal : 1.
INSTALLATION (7) Set the node address before replacing the cover onto the inverter. (Refer to page 7 for node address setting.) (8) Next remove the option data port insert from the inverter cover. Then replace the inverter cover, while making sure that the Modbus Plus connector is aligned with the option data port window. Connect the Modbus Plus cable to the inverter by plugging DB9-style male connector into DB9-style female connector of the option unit, which should be visible in the option port window.
INSTALLATION 2.2 Node address setting (1) Make sure that the inverter power is off and the option unit is mounted in the inverter. Connect the Modbus Plus cable you created to the network. (2) When setting the Modbus Plus address on the option board, use the following table. Refer to page 2 for the address switch location. REMARKS A switch setting of 1 indicates the On position, and a switch setting of 0 indicates the Off position.
INSTALLATION Decimal Address Switch Positions 4 5 0 0 0 0 0 0 0 0 0 0 1 1 28 29 30 31 32 33 1 0 1 0 1 0 1 2 0 1 1 0 0 1 3 1 0 0 0 0 1 34 35 36 37 38 39 0 1 0 1 0 1 1 0 0 1 1 0 1 1 1 0 0 0 1 1 1 1 1 1 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 1 1 0 0 0 0 1 1 1 1 0 0 0 0 1 1 1 1 0 0 0 1 0 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1 0 0 0 0 0 0 0 8 6 1 1 1 1 1 0 7 1 1 1 1 1 1
INSTALLATION Alternate method for setting the switch: i. ii. iii. iv. To set the node address to be nn, first subtract 1 from it. Convert the result (nn-1) into hexadecimal XXh. Then span it into binary format, padding with 0's in the front 00fedcba. Finally, take the complement 11nmlkji, if a bit is 0, set the switch to Off position; if a bit is 1, set the switch to On position. REMARKS The first two leading position switches are not used.
INSTALLATION 2.3 Communication cable When making a cable for the Modbus Plus protocol, make sure that each end of the cable is terminated with the A5MBKT185 terminator connectors. For nodes between the termination points, use the in-line connectors (A5MBKT085). The cable should be a Modbus Plus standard cable (490NAA271xxF). Connect a wire from the ground terminal on the FR-A5NM to the inverter Chassis to ensure proper grounding of the option board.
INSTALLATION Please connect Modbus connector and the communication cable following the table.
3. OPERATION The operation of the inverter changes slightly when you install this option unit, as described below. 3.1 Operating Modes In the PU operating mode, a Parameter Unit (PU) controls the inverter. In the External-operating mode, the inverter is controlled by external signals connected to the inverter's terminal block. In the Network (computer link) operating mode, the inverter is controlled by commands from a Modbus Plus master. 3.
OPERATION 3.3 Functions Available in the Operating Modes The functions available to the drive depend on the operating mode. The following table indicates the command types available according to the operating mode.
4. ACCESSING DRIVE DATA (1) This option unit acts as a Modbus Plus slave to a PLC or equivalent controller acting as a Modbus Plus master. This means that the option unit: • Acknowledges messages received • Transmits messages at the request of a network master. (2) The option unit can also act as a Modbus Plus slave to a Modbus Plus master that can read the drive's I/O values, as well as configure the drive itself. (3) The option unit cannot send messages on its own, and it has no bus access rights.
5. PARAMETER DEFINITIONS Depending upon which Modbus Plus master device is being used, data registers may be referenced using a 5-digit(4nnnn) or 6-digit(40nnnn) format. For convenience, this manual uses the 5-digit format. When using the 6-digit format, the last 4 digits of the register remain the same and a zero is inserted between the numeral 4 and the 4-digit register number(nnnn). The Modbus Plus option card generates error codes when inappropriate operations occur.
PARAMETER DEFINITIONS Read out data: FFFEh means No parameter. FFFDh means parameter Not Available. Any register that does not appear in any entry of the following tables is considered Reserved.
PARAMETER DEFINITIONS 5.1 Input to Inverter From Modbus Plus Network (Control Input Command) To change the inverter Control Input Cmd, write the word value to Register 40009. The following table describes the bit-map for the inverter Ctrl Input Cmd word value. Write a value to register 40009 to give an operation command to the inverter. The bit-map values of the control instructions to the inverter are listed in the following table.
PARAMETER DEFINITIONS 5.2 Output From Inverter to Modbus Plus Network (Inverter Status) To check the inverter status, read the word out from Register 40009 or 40019. The following table describes the bit-map for the inverter status word.
PARAMETER DEFINITIONS 5.
PARAMETER DEFINITIONS 5.4 Using the Modsoft MSTR Block The MSTR control register usage is as follows: PLC Register Register Value Value Base Description Commands MSTR function: 1 = write; 2 = read n+1 xxxx hexadecimal MSTR function error code Number of registers to be written/read n+2 1 decimal to /from the inverter Specifies the inverter register to write/ read to/from. Value represents an n+3 rrrr decimal offset starting w/register 40000 (i.e. 1 = 40001; 49 = 40049).
PARAMETER DEFINITIONS Register 40215 40216 40217 40218 40219 40220 40222 40223 40224 40225 Minimum Setting Minimum Setting Increments Increments (A500, F500) (A500L, F500L) — — RTM15 Inp Termnl Status (*1) RTM16 Outp Termnl Status (*2) — — RTM17 Load Meter 0.1% 0.1% RTM18 Motor Excitatn I 0.01A 0.1A RTM19 Positive Pulse — — RTM20 Cumulative Energ t 1h 1h RTM22 Orientatn Status — — RTM23 Actl Op t 1h 1h RTM24 Motor Load Factr 0.1% 0.
PARAMETER DEFINITIONS 5.6 Input/Output Terminal Assignment CAUTION Input/output terminal assignment functions depend upon programmed functions such as brake sequences 5.7 Operation When an Alarm Occurs The following table shows the behavior of the inverter and network when an alarm occurs: Fault Type Inverter (*2) Modbus Plus Comm. (*3) Item Inverter Operation Network Comm.
PARAMETER DEFINITIONS 5.8 Alarm History Register 40501 40502 40503 40504 40505 40506 40507 40508 Definition Alarm 1 (*1) Alarm 2 Alarm 3 Alarm 4 Alarm 5 Alarm 6 Alarm 7 Alarm 8 *1 Writing any value to parameter 40501 resets the alarm history buffer for all alarms. All other entries in this table are read only. 5.9 Alarm Numbers vs.
PARAMETER DEFINITIONS 5.10 A500(L) PARAMETERS 5.10.1 Normal Parameter Area You can use the Register to make parameter settings from the network. The last three digits of Register are the parameter number. Standard parameter examples are introduced below. Refer to the examples and make parameter settings. For the parameter data and details, refer to the inverter and option manuals.
PARAMETER DEFINITIONS 5.11 900f Parameter Area Parameter Register Pr. 902 41902 Pr. 903 41903 Pr. 904 41904 Pr. 905 41905 Definition Pr. 902f Frequency Setting Voltage Bias (frequency) Frequency Setting Voltage Gain (frequency) Frequency Setting Current Bias (frequency) Frequency Setting Current Gain (frequency) 5.12 900% Parameter Area Parameter Pr. 902 Pr. 903 Pr. 904 Pr.
PARAMETER DEFINITIONS 5.13 Programmed Operation : Setting Time Parameter Pr. 200 Pr. 201 Pr. 202 Pr. 203 Pr. 204 Pr. 205 Pr. 206 Pr. 207 Pr. 208 Pr. 209 Pr. 210 Pr. 211 Pr. 212 Pr. 213 Pr. 214 Pr. 215 Pr. 216 Pr. 217 Pr. 218 Pr. 219 Pr. 220 Pr. 221 Pr. 222 Pr. 223 Pr. 224 Pr. 225 Pr. 226 Pr. 227 Pr. 228 Pr. 229 Pr. 230 Pr.
PARAMETER DEFINITIONS 5.14 Programmed Operation : Setting Rotation Direction Parameter Pr. 201 Pr. 202 Pr. 203 Pr. 204 Pr. 205 Pr. 206 Pr. 207 Pr. 208 Pr. 209 Pr. 210 Pr. 211 Pr. 212 Pr. 213 Pr. 214 Pr. 215 Pr. 216 Pr. 217 Pr. 218 Pr. 219 Pr. 220 Pr. 221 Pr. 222 Pr. 223 Pr. 224 Pr. 225 Pr. 226 Pr. 227 Pr. 228 Pr. 229 Pr.
PARAMETER DEFINITIONS 5.15 Programmed Operation : Frequency Setting Parameter Pr. 201 Pr. 202 Pr. 203 Pr. 204 Pr. 205 Pr. 206 Pr. 207 Pr. 208 Pr. 209 Pr. 210 Pr. 211 Pr. 212 Pr. 213 Pr. 214 Pr. 215 Pr. 216 Pr. 217 Pr. 218 Pr. 219 Pr. 220 Pr. 221 Pr. 222 Pr. 223 Pr. 224 Pr. 225 Pr. 226 Pr. 227 Pr. 228 Pr. 229 Pr.
6. SPECIFICATIONS Current Consumption Backplane Isolation Supported Data Rates Operating Temperature Storage Temperature (*1) Relative Humidity Dimensions From inverter drive:300 mA typ. @5 Vdc Provided to Modbus Plus network:100 mA @5 Vdc 500 Vdc min. <= 450 m: 1 M bps, no repeater; <= 1800 m: 1 M bps, repeaters Maximum distance between nodes is 450 meters. -10 to 50 °C -20 to 65 °C <= 90% @50 °C, non-condensing 96 x 49 x 33 mm *1 This refers to a short period of time such as during transportation.
Appendix A. Other Option-Specific parameters The following table identifies option-specific parameters which are used for the A5NM. Pr. # Function Setting Range 338 339 340 Operation control command source Speed command source Link start-up mode selection 0, 1 0, 1 0, 1, 2* Minimum Default Increment Setting 1 0 1 0 1 0 * Pr.340 "link startup mode selection" can be switched from the PU in any operation mode. A. Definition for Pr. 338 and Pr. 339 Control Source Selection Function Pr. Pr.
MEMO
REVISIONS *The manual number is given on the bottom left of the back cover. Print Date *Manual Number Mar., 2003 Nov.