User`s manual

5-18 INP-TN5A0202-E
5.4 Status Display
5.4
Status Display
The status display is the parameter in order to monitor the programless communication module operation.
The status display is con rmed by reading out from the front face loader port or registering to the PLC monitor area. (Set the
“Monitor area entry St. No.” parameter to “128” when entry for the monitor area.)
Communication module status
The programless communication module operation status can be referred.
Refer to the parameters below.
Parameter Unit Attribute
MODBUS register No.
(Relative Address)
Setting error None R 30232 (00E7h)
Parameters’ explanation
Parameter setting error
When the parameter read out from the EEPROM is the invalid value, the error code is stored.
Error code Explanation
0101h St. No. con guration SW is invalid value
0102h DIP SW is invalid value
0201h PLC communication speed is invalid value
0202h PLC transmission setting is invalid value
0203h MC protocol is invalid value
0204h PLC communication inter-cycle is invalid value
0205h PLC communication starting time is invalid value
0206h PLC response monitoring time is invalid value
0207h Number of PLC communication retry is invalid value
0208h Connection method is invalid value (Not used)
0209h Number of connected units is invalid value (Not used)
020Ah Operation at PLC communication fault is invalid value
020Ch MC protocol frame type is invalid value
0210h Setting area device type is invalid value
0211h Setting area device size is invalid value
0212h Monitor area device type is invalid value