User`s manual
INP-TN5A0202-E 5-9
5.2 Memory Setting
Communication parameter entr y (Monitor area)
Register a module type temperature controller parameter reading out from PLC with a programless communication as the
combination of the “Monitor area entry St. No.” parameter and the “Monitor area entry register No.” parameter.
Refer to the parameters below.
Parameter Setting Range Unit
Factory-set
value
Attribute
MODBUS register No.
(Relative Address)
Monitor area entry St. No.
The 1
st
word
0 : Not used
1 to 16 : Control/Analog
module
17 to 32 : Event module
128 : Programless
communication
module
None 0 R/W 43001 (0BB8h)
Monitor area entry
register No. The 1
st
word
0,30000 to 49999 (*) None 0 R/W 43002 (0BB9h)
.
.
.
Monitor area entry St. No.
The 712
th
word
0 : Not used
1 to 16 : Control/Analog
module
17 to 32 : Event module
128 : Programless
communication
module
None 0 R/W 44423 (1146h)
Monitor area entry
register No. The 712
th
word
0,30000 to 49999 (*) None 0 R/W 44424 (1147h)
* Only the address written in the “Setting/Monitor area register No.” (Control module
5-51
,
Event module
5-64
,
Analog module
5-71
) is settable. However, the parameter marked “*” in the “Entry ban” column cannot be set.
Note
Number of registerable parameters per reference station is limited. Also, please note that maximum number of registerable
parameters is depends on each module shown below.
Modeule Type Maximum No.
Control module 32
Analog I/O module 32
Event I/O module 8
Programless communication module No limit
If register parameters more than the maximum number, the PWR indicator will blink red (0.4-sec inter-cycle), and then comes
to be in the communication fault status.