User`s manual

5-6 INP-TN5A0202-E
5.2 Memory Setting
Communication parameter entr y (Setting area)
Register the module type temperature controller parameter writing from a PLC with a combination of “Setting area entry St. No.”
parameter and the “Setting area entry register No.” parameter with a programless communication.
Refer to the parameters below.
Parameter Setting Range Unit
Factory-set
value
Attribute
MODBUS register
No.(Relative Address)
Setting area entry St. No.
The 1
st
word
0: Not used
1 to 16: Control/Analog
module
17 to 32: Event module
None 0 R/W 41001 (03E8h)
Setting area entry
register No. The 1
st
word
0,40000 to 49999 (*) None 0 R/W 41002 (03E9h)
.
.
.
Setting area entry St. No.
The 712
th
word
0: Not used
1 to 16: Control/Analog
module
17 to 32: Event module
None 0 R/W 42423 (0976h)
Setting area entry
register No. The 712
th
word
0,40000 to 49999 (*) None 0 R/W 42424 (0977h)
* Only the address written in “Setting/Monitor area register number” (Control module
5-51
, Event module
5-64
, Analog module
5-71
) settable. However, the monitor parameters and parameter marked “*” in the
“Entry ban” column cannot be set.
Note
Number of registerable parameters per reference station is limited. Also, please note that maximum number of registerable
parameters is depends on each module shown below.
Modeule Type Maximum No.
Control module 32
Analog I/O module 32
Event I/O module 8
If register parameters more than the maximum number, the PWR indicator will blink red (0.4-sec inter-cycle), and then comes
to be in the communication fault status.