5.1 Programless Communication Module Operation Setting
Operation setting when a programless communication fault occurs
The parameter below sets the operation when a programless communication fault occurs.
Refer to the parameters below.
Parameter Setting Range Unit
Factory-set
value
Attribute
MODBUS Register No.
(Relative Address)
Operation selection
when a programless
communication fault
occurs
0000h: RUN
0001h: STOP
None 0001h R/W 40010 (0009h)
When set “0000h (RUN) to “Operation selection when a programless communication fault occurs”, if the communication between
PLC and a programless communication module is restored to be in a normal state, the programless communication will recover
automatically and the same operation as it did is continued.
When set “0001h (STOP)” to “Operation selection when a programless communication fault occurs”, even if the communication
between a PLC and a programless communication module is restored to be in a normal state, the programless communication
will be in a stopped state. In order to restart a programless communication, use Communication restoration demand.