User`s manual

INP-TN5A0202-E 5-3
5.1 Programless Communication Module Operation Setting
5.1
Programless Communication
Module Operation Setting
Explanation here is for performing programless communications with a programless communication module.
Programless communication module station number con guration switch
Setting a station number of a programless communication module. Apply a fine tip flat-head screwdriver to turn the station
number con guration switch.
Setting range 1:1 connection = 0 (fixed)
1:N connection = 0 to 7
(factory-set value = 0)
LOADER
PUM-C
PWR
BUS
RX1
TX1
RX2
TX2
STATION
4
3
2
1
0
F
E
D
C
B
A
9
8
7
6
5
STATION
4
3
2
1
0
F
E
D
C
B
A
9
8
7
6
5
Note
When performs programless communication with 1:1 connection, make sure to set "0" to the station number of this
equipment. Otherwise, this equipment can not perform communication with PLC.
When performs programless communication with 1:N connection, make sure to set station numbers of this equipment in
order, from "0". If there are missing numbers with the station numbers, this equipment can not perform communication
normally with PLC.