User`s manual
4-20
4.3 Parameter Setting Demand/Response Flag
INP-TN5A0202-E
Continuous writing (Command: 0002h)
Setting "0002h" for the system fi eld "parameter setting fl ag" in the device memory setting area enables the value of data fi eld in
the setting area to be written periodically to the temperature control module parameter entered as the setting parameter.(Refer to
"PLC communication inter-cycle time"
5-14
about the periodical time).
Write set value to each temperature control module
Set value Set value
PLC
(3) If completed the writing,
“0002h” will be set to the
parameter setting response flag.
(2) Write set value to the temperature
control module continuously
(1) If “0002h” is set for the parameter setting
demand flag, the writing command
will be set continuously
Temperature
control module
St.32
(When connected
max. units)
Temperature
control module
St.1
Setting area
field
Device memory
Monitor area
System field
Data field
Setting area
System field
Data field
Programless
communication
module
Execute the stop operation command
4-18
and put the programless communication module to the standby state in
order to stop continuous reading out.