3.6 Connection
INP-TN5A0202-E
RS-485 connection
1:1 connection
Communication unit This unit
Terminating resistance
Terminating resistance
Signal Pin No. Signal
SDA 21 TX
SDB 22 RX
RDA 23 SG
RDB 24 A
SG 25 B
FG 26 SG
27 A
RS-422/RS-485 cable
28 B
29
30
1:N connection
Communication unit This unit 1 This unit 2
Terminating resistance
Terminating resistance
Signal Pin No. Signal Pin No. Signal
SDA 21 TX 21 TX
SDB 22 RX 22 RX
RDA 23 SG 23 SG
RDB 24 A 24 A
SG 25 B 25 B
FG 26 SG 26 SG
27 A 27 A
RS-422/RS-485 cable
28 B 28 B
29 29
30 30
Use the terminal insulation shown as below.
RS-422 : 330Ω ±5% 1/2W
RS-485 : 110Ω ±5% 1/2W
This unit can not make 2 or more different communication connections operate at the same time.
Connecting modules
Connectable modules to the equipment are as follows.
PUMA/B (Control module), PUMV/N/T (Analog I/O module), PUME (Event I/O module)
Max. 32 units are connectable to the equipment. The number of connectable modules varies according to module types.
Refer to user’s manual for each module for details.
When connected modules, power supplies are connected to other modules by connecting power supply lines to the one of
the modules.