User`s manual

3-19
3.6 Connection
INP-TN5A0202-E
Setting of MELSEC-A series
Refer to the Instruction Manual of Computer link module for setting.
Ex.) A1SJ71UC24-R4
Transmission speci cation setting switch
SW Setting items
State
Set value
OFF ON
1 Not used ――
2 Select Computer/Multi-drop link Not settable Computer link ON ( xed)
3 Not used ――
4 Write during RUN No Yes ON ( xed)
5
Transmission speed *3 *16
7
8 Data bit setting 7 bits 8 bits ON ( xed)
9 Parity bit No Yes *2
10 Odd/Even parity setting Odd Even *2
11 Stop bit setting 1 bit 2 bits *2
12 Sum check No Yes ON ( xed)
*1 Same setting should be made as "PLC communication speed setting" parameters
5-11
of a programless
communication module.
*2 Same setting should be made as "PLC transmission setting" parameters
5-12
of a programless communication
module.
*3 Transmission speed setting
Setting SW 9600 19200 Setting forbidden
5 ON OFF ON
6 OFF ON ON
7 ONONON
St. No. con guration SW
Name Contents Set value
×10 Set the tenths place digit 0 ( xed)
×1 Set the ones place digit 0 ( xed)
Mode setting SW
SW Setting
0 Not available
1 Not available
2 Not available
3 Not available
4 Not available
5 Not available
6 Dedicated protocol Type2
7 Not available
8 Dedicated protocol Type4
9 to F Not available