User`s manual
4
INP-TN5A0202-E
Locations in contact with water, oil, chemicals, steam or
hot water.
(If the equipment gets wet, there is a risk of electric shock
or fi re, so have it inspected by Fuji distributor.)
Locations with high concentrations of atmospheric dust,
salt or iron particles.
Locations with large inductive interference, resulting in
static electricity, magnetic fi elds or noise.
Locations in direct sunlight.
Locations that build up heat from radiant heat sources,
etc.
A switch or circuit breaker shall be included in the building
installation. Please be it in close proximately to the
equipment and within easy reach of the operator, and
mark it as the disconnecting device for the equipment.
Cautions when Mounting to Cabinets/DIN Rails
In case of mounting the temperature controllers to DIN
rails, remember to push up the locking tabs to fasten the
controllers onto DIN rail.
To connect controllers, fi rst release all locking tabs. Then,
connect controllers and push up all locking tabs. Make
sure that all locking tabs are fastened.
Never fail to turn the power OFF, before detaching the
terminal block or removing the main unit from the base
part.
In order to aid heat dissipation, do not block the top and
the bottom of the equipment.
When mounting/dismounting controllers to /from DIN
rails, 30mm of clearance above and under the controllers
should be provided.
Cautions for Wiring
For wiring to the terminal block, apply crimp type terminals
size M3.
Use terminal screws in this product only.
Screw size: M3×7 (with square washer)
Screw tightening torque: 0.78 N • m (8kgf • cm)
To avoid the infl uence of inductive noise, input signal wires
should be separated from electric power lines or load
lines.
To use the RS-232C communication, attach noise filters
to the AC power lines. (Not necessary, provided that the
noise suppression of the power line is thoroughgoing)
To comply with CE marking (EMC), we recommend to
attach ferrite core to communication cable and power
cable.
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Error Operation
The alarm function does not work properly when an error
occurs unless the settings are made correctly. Always
verify its setting before operation.
Others
Please do not wipe the equipment with organic solvents
such as alcohol or benzene, etc. If wiping is necessary,
use a neutral cleaning agent.
Do not use mobile phones near this equipment (within
50cm). Otherwise a malfunction may result.
Malfunctions may occur if the equipment is used near a
radio, TV, or wireless device.
This equipment requires approx. 5 to 30 seconds before it
starts to output.
Before installing and wiring, take necessary measures for
electrostatic discharge (ESD).
The power supply for this product is 24V DC. Please use
the power source of appropriate volume depending on the
number of units you connect.
Recommended power supply:
Cosel Electronics Co., Ltd. PBA Series
Omron Corporation S8VM Series
•
•
•
•
•
•
•