User`s manual

7-6 INP-TN5A0202-E
7.1 Error procedure
Troubles Causes Solutions
PWR indicator:
GREEN blinking
during 1:N connection
(0.1-sec inter-cycle)
PLC communication speed and
PLC communication data length is
mismatch
Check PLC communication speed setting/
PLC data length setting of the programless
communication module matches the
communication setting of PLC
The master station (St. No. "0") for
1:N connection is not connected
Connect the programless communication
module which St. No. is "0"
Only some programless
communication modules which are
connected during 1:N connection
cannot perform a programless
communication
There are some programless
communication modules that settings
below differ
PLC communication speed
PLC communication data length
MC protocol
PLC communication inter-cycle
time
PLC response monitoring time
Connection method
No. of connected units
MC protocol frame type
Correct the set value with PUM parameter
loader and restart
Written value to PLC device
is sent to several programless
communication modules
With 1:N connection, the setting area
device memory setting of PLC is
duplicated
Make the setting area device memory
setting of each programless communication
module not to be duplicated
The value of Inter-PLC
communication execution time
monitor came to be extremely big
during 1:N connection
Other connected programless
communication modules were in the
communication error state (ex. break)
Restore the programless communication
module that is in the communication error
state, and restart