User`s manual
INP-TN5A0202-E 5-81
5.8 Setting/Monitor Area Entry Numbers (Analog module)
Confi guration Parameters
Contents
Readout/Write data
setting range
Depends
on input
range
Factory-
set
value
Register
No. 1
(Ch1)
Register
No. 2
(Ch2)
Register
No. 3
(Ch3)
Register
No. 4
(Ch4)
Entry
ban
Aio Ai Ao
LED2 lamp allocation 0 to 255 1 40222
*
ccc
LED3 lamp allocation 0 to 255 12 40223
*
LED4 lamp allocation 0 to 255 13 40224
*
LED5 lamp allocation 0 to 255 14 40225
*
LED6 lamp allocation 0 to 255 15 40226
*
Reset main unit 0: Do nothing
1: Reset main unit
0 40101
*
Monitor Parameters
Note
Monitor parameters can enter for the monitor area only. Do not enter the setting area.
Contents
Readout/Write data
setting range
Depends
on input
range
Factory-
set
value
Register
No. 1
(Ch1)
Register
No. 2
(Ch2)
Register
No. 3
(Ch3)
Register
No. 4
(Ch4)
Entry
ban
Aio Ai Ao
System time 0 to 65535 - 30001
cc¯
Input value (Analog
input)
-5 to 105% FS - 30002
31001
30003
32001
30004
33001
30005
34001
RCJtemp -3276.7 to 3276.7°C - 30110
31016
30111
32016
30112
33016
30113
34016
Error source display 0 to FFFF - 31008 32008 33008 34008
Alarm 1-5 status 0 to 001F - 31007 32007 33007 34007
Event input status 0 to FFFF - 31061 32061 33061 34061
Remaining time on
timer 1
0 to 99 min. 59 sec.
/0 to 99hr. 59 min.
- 31011 32011 33011 34011
Remaining time on
timer 2
0 to 99 min. 59 sec.
/0 to 99hr. 59 min.
- 31012 32012 33012 34012
Remaining time on
timer 3
0 to 99 min. 59 sec.
/0 to 99hr. 59 min.
- 31013 32013 33013 34013
Remaining time on
timer 4
0 to 99 min. 59 sec.
/0 to 99hr. 59 min.
- 31014 32014 33014 34014
Remaining time on
timer 5
0 to 99 min. 59 sec.
/0 to 99hr. 59 min.
- 31015 32015 33015 34015
Output value (Analog
outout)
-3.0 to 103.0% - 30120 30121 30122 30123
c¯c
RS-485 Communication
permission
0: Read only
1: Read/Write
- 30062
ccc