User`s manual
INP-TN5A0202-E 5-77
5.8 Setting/Monitor Area Entry Numbers (Analog module)
Alarm Parameter
Contents
Readout/Write data
setting range
Depends
on input
range
Factory-
set
value
Register
No. 1
(Ch1)
Register
No. 2
(Ch2)
Register
No. 3
(Ch3)
Register
No. 4
(Ch4)
Entry
ban
Aio Ai Ao
ALM1 hysteresis 0 to 50% FS
c
0.25% FS 41035 42035 43035 44035
cc¯
ALM1 delay time 0 to 99 min. 59sec.
/0 to 99hr. 59min.
0 41037 42037 43037 44037
ALM1 delay time units 0: sec.
1: min.
0
(Second)
41038 42038 43038 44038
ALM2 hysteresis 0 to 50% FS
c
0.25% FS 41043 42043 43043 44043
ALM2 delay time 0 to 99 min. 59sec.
/0 to 99hr. 59min.
0 41045 42045 43045 44045
ALM2 delay time units 0: sec.
1: min.
0
(Second)
41046 42046 43046 44046
ALM3 hysteresis 0 to 50% FS
c
0.25% FS 41051 42051 43051 44051
ALM3 delay time 0 to 99 min. 59sec.
/0 to 99hr. 59min.
0 41053 42053 43053 44053
ALM3 delay time units 0: sec.
1: min.
0
(Second)
41054 42054 43054 44054
ALM4 hysteresis 0 to 50% FS
c
0.25% FS 41059 42059 43059 44059
ALM4 delay time 0 to 99 min. 59sec.
/0 to 99hr. 59min.
0 41061 42061 43061 44061
ALM4 delay time units 0: sec.
1: min.
0
(Second)
41062 42062 43062 44062
ALM5 hysteresis 0 to 50% FS
c
0.25% FS 41067 42067 43067 44067
ALM5 delay time 0 to 99 min. 59sec.
/0 to 99hr. 59min.
0 41069 42069 43069 44069
ALM5 delay time units 0: sec.
1: min.
0
(Second)
41070 42070 43070 44070
Object Ch. No. for
interchannel ALM1
1 to 4 1 41039 42039 43039 44039
Object Ch. No. for
interchannel ALM2
1 to 4 1 41047 42047 43047 44047
Object Ch. No. for
interchannel ALM3
1 to 4 1 41055 42055 43055 44055
Object Ch. No. for
interchannel ALM4
1 to 4 1 41063 42063 43063 44063
Object Ch. No. for
interchannel ALM5
1 to 4 1 41071 42071 43071 44071