User`s manual

5-74 INP-TN5A0202-E
5.8 Setting/Monitor Area Entry Numbers (Analog module)
System Parameters
Contents
Readout/Write data
setting range
Depends
on input
range
Factory-
set
value
Register
No. 1
(Ch1)
Register
No. 2
(Ch2)
Register
No. 3
(Ch3)
Register
No. 4
(Ch4)
Entry
ban
Aio Ai Ao
Current output range 4: 0 to 20mA
5: 4 to 20mA
5
(4-20mA
)
40166
41801
40167
42801
40168
43801
40169
44801
c¯c
Output type 0: Ai of own station
1: Output 0%
2: Output 0%
3: Output 0%
4: Internal analog output
eld
5: PV of other St.
6: SV of other St.
7: MV of other St.
3
(output
0%
)
40171
41803
40177
42803
40183
43803
40189
44803
Output master St. 0 to 255 stations 0 40172
41804
40178
42804
40184
43804
40190
44804
*
Output master Ch. 1 to 4Ch Each Ch. 40173
41805
40179
42805
40185
43805
40191
44805
*
Output scaling base -100.0 to 100.0% 0.0 40175
41807
40181
42807
40187
43807
40193
44807
Output scaling span -100.0 to 1000.0 100.0 40174
41806
40180
42806
40186
43806
40192
44806
Output shutdown 0000 to 1111
bit 0 : Output 1 shutdown
bit 1 : Output 2 shutdown
bit 2 : Output 3 shutdown
bit 3 : Output 4 shutdown
0000 40201
DI-1 function select 0: No function
1: RUN/Standby SW
2: No function
3: No function
4: No function
5: No function
6: No function
7: No function
8: No function
9: No function
10: No function
11: No function
12: No function
13: No function
14: No function
15: No function
16: No function
17: Latch release (all)
18: Latch release (DO1)
19: Latch release (DO2)
20: Latch release (DO3)
21: Latch release (DO4)
22: Latch release (DO5)
23: No function
0 41013 42013 43013 44013