User`s manual
5-72 INP-TN5A0202-E
5.8 Setting/Monitor Area Entry Numbers (Analog module)
Setup Parameters
Contents
Readout/Write data
setting range
Depends
on input
range
Factory-
set
value
Register
No. 1
(Ch1)
Register
No. 2
(Ch2)
Register
No. 3
(Ch3)
Register
No. 4
(Ch4)
Entry
ban
Aio Ai Ao
Analog input type 0: JPt100(0 to 150°C)
1: JPt100(-150 to 600°C)
2: Pt100(0 to 150°C)
3: Pt100(-150 to 300°C)
4: Pt100(-150 to 850°C)
5: J(0 to 400°C)
6: J(0 to 800°C)
7: K(0 to 400°C)
8: K(0 to 800°C)
9: K(0 to 1200°C)
10: R(0 to 1600°C)
11: B(0 to 1800°C)
12: S(0 to 1600°C)
13: T(-199 to 400°C)
14: E(-199 to 800°C)
18: N(0 to 1300°C)
19: PL-2(0 to 1300°C)
21: Voltage (0 to 5V)
22: Voltage (1 to 5V)
23: Voltage (0 to 10V)
24: Voltage (2 to 10V)
7
(
TC/Pt
)
22
(
VI
)
40151
41029
40152
42029
40153
43029
40154
44029
*
cc¯
Analog input scale
lower
-1999 to 9999 0% FS 41212 42212 43212 44212
*
Analog input scale
upper
-1999 to 9999 100% FS 41213 42213 43213 44213
*
Decimal place 0: No decimal point
1: One decimal place
2: Two decimal places
0
(
TC/Pt
)
1
(
VI
)
41214 42214 43214 44214
*
Temperature unit 0: Degree C
1: Not selectable
0
(
°C) 41215 42215 43215 44215
*
Analog input shift -10 to 10% FS
c
0 41216 42216 43216 44216
Analog input fi lter 0.0 to 120.0sec 2.0 41220 42220 43220 44220
Analog input
display
zero adjustment
-50 to 50% FS
c
0 41221 42221 43221 44221
Analog input
display
span adjustment
-50 to 50% FS
c
0 41222 42222 43222 44222
Cold junction
compensation
0: OFF
1: ON
1
(
ON
)
41223 42223 43223 44223