5.8 Setting/Monitor Area Entry Numbers (Analog module)
5.8
Setting/Monitor Area Entry
Numbers (Analog module)
The table below shows the register numbers of an analog module, which are settable to each parameter of "Setting/Monitor
area entry St. No." and "Setting/Monitor area entry register No." of a programless communication module.
Note
Parameters marked "*" in the "Entry ban" column in the table can not be changed via programless communication modules.
Do not set them to each parameter of "Setting/Monitor area entry St. No." and "Setting/Monitor area entry register No."
Operation Parameters
Contents
Readout/Write data
setting range
Depends
on input
range
Factory-
set
value
Register
No. 1
(Ch1)
Register
No. 2
(Ch2)
Register
No. 3
(Ch3)
Register
No. 4
(Ch4)
Entry
ban
Aio Ai Ao
RUN/Standby SW 0: RUN
1: Standby
0 (RUN) 40017
41004
40018
42004
40019
43004
40020
44004
ccc
Internal analog
output eld
-327.6 to 327.6
0 40251 40252 40253 40254
c¯c
Digital output latch
release command
0: OFF
1: Release latch
0 (OFF) 41031 42031 43031 44031
cc¯
ALM1 set value 1 -100 to 100% FS
c
2.5% FS 41033 42033 43033 44033
ALM1 set value 2 -100 to 100% FS
c
2.5% FS 41034 42034 43034 44034
ALM2 set value 1 -100 to 100% FS
c
2.5% FS 41041 42041 43041 44041
ALM2 set value 2 -100 to 100% FS
c
2.5% FS 41042 42042 43042 44042
ALM3 set value 1 -100 to 100% FS
c
2.5% FS 41049 42049 43049 44049
ALM3 set value 2 -100 to 100% FS
c
2.5% FS 41050 42050 43050 44050
ALM4 set value 1 -100 to 100% FS
c
2.5% FS 41057 42057 43057 44057
ALM4 set value 2 -100 to 100% FS
c
2.5% FS 41058 42058 43058 44058
ALM5 set value 1 -100 to 100% FS
c
2.5% FS 41065 42065 43065 44065
ALM5 set value 2 -100 to 100% FS
c
2.5% FS 41066 42066 43066 44066