User`s manual
INP-TN5A0202-E 5-69
5.7 Setting/Monitor Area Entry Numbers (Event I/O module)
Contents
Reading out/Writing data setting
range
Factory-set
value
Register No.
Entry
ban
DO8 output limit (upper) 0.0 - 100.0 1000 40511
DO8 limit type 0-3 0 40512
Communication Parameters
Contents
Reading out/Writing data setting
range
Factory-set
value
Register No.
Entry
ban
RS-485 parity setting 0: None
1: Odd
2: Even
0 40111
*
RS-485 response interval time 0 to 25 (1digit/20ms) 1 40113
*
RS-485 communication permission 0: Ready only
1: Read/Write
1 40114
*
RS-485 communication speed 0: 9.6kbps
1: 19.2kbps
2: 38.4kbps
3: Forbidden
4: 115.2kbps
1 40115
*
Enhanced communication module (PUMC)
connection permission
0: PUMC not connected
(RS-485 Enable)
1: PUMC connected (RS-485 Disable)
0 40116
*
Confi guration Parameters
Contents
Reading out/Writing data setting
range
Factory-set
value
Register No.
Entry
ban
FAULT output 1 set value 0: HOLD
1: OFF
0 40260
Standby output set value 0000-FFFF 0 40268
Standby mode setting 0: DI=input value
DO= Standby output set value
1: DI=All OFF
DO=Standby output set value
0 40270
LED2 Lamp confi guration 0-2 1 40222
*