User`s manual
INP-TN5A0202-E 5-67
5.7 Setting/Monitor Area Entry Numbers (Event I/O module)
Contents
Reading out/Writing data setting
range
Factory-set
value
Register No.
Entry
ban
DO3 output option 0-15 0 40433
DO3 output logic operation AND 0-00FF 0 40435
DO3 output logic operation OR 0-00FF 0 40436
DO3 scaling base -100.0 - +100.0 0 40437
DO3 scaling span -100.0 - +100.0 1000 40438
DO3 proportion cycle 1-120 30 40439
DO3 output limit (lower) 0.0 - 100.0 0 40440
DO3 output limit (upper) 0.0 - 100.0 1000 40441
DO3 limit type 0-3 0 40442
DO4 output type 0: Event output
1: Control output
0 40443
*
DO4 master St. No. 0-255 0 40444
*
DO4 master Ch. No. 1-4 1 40445
*
DO4 BIT position 0-FFFF 8 40446
DO4 output option 0-15 0 40447
DO4 output logic operation AND 0-00FF 0 40449
DO4 output logic operation OR 0-00FF 0 40450
DO4 scaling base -100.0 - +100.0 0 40451
DO4 scaling span -100.0 - +100.0 1000 40452
DO4 proportion cycle 1-120 30 40453
DO4 output limit (lower) 0.0 - 100.0 0 40454
DO4 output limit (upper) 0.0 - 100.0 1000 40455
DO4 limit type 0-3 0 40456
DO5 output type 0: Event output
1: Control output
0 40457
*
DO5 master St. No. 0-255 0 40458
*
DO5 master Ch. No. 1-4 1 40459
*
DO5 BIT position 0-FFFF 16 40460
DO5 output option 0-15 0 40461
DO5 output logic operation AND 0-00FF 0 40463
DO5 output logic operation OR 0-00FF 0 40464
DO5 scaling base -100.0 - +100.0 0 40465
DO5 scaling span -100.0 - +100.0 1000 40466
DO5 proportion cycle 1-120 30 40467
DO5 output limit (lower) 0.0 - 100.0 0 40468
DO5 output limit (upper) 0.0 - 100.0 1000 40469
DO5 limit type 0-3 0 40470
DO6 output type 0: Event output
1: Control output
0 40471
*