User`s manual

5-66 INP-TN5A0202-E
5.7 Setting/Monitor Area Entry Numbers (Event I/O module)
Digital Output Parameters
Contents
Reading out/Writing data setting
range
Factory-set
value
Register No.
Entry
ban
DO1 output type 0: Event output
1: Control output
0 40401
*
DO1 master St. No. 0-255 0 40402
*
DO1 master Ch. No. 1-4 1 40403
*
DO1 BIT position 0-FFFF 1 40404
DO1 output option Bit 0 : LATCH
Bit 1 : NOT
Bit 2 : AND
Bit 3 : OR
0 40405
DO1 output logic operation AND 0-00FF 0 40407
DO1 output logic operation OR 0-00FF 0 40408
DO1 scaling base -100.0 - +100.0 0 40409
DO1 scaling span -100.0 - +100.0 1000 40410
DO1 proportion cycle 1-120 30 40411
DO1 output limit (lower) 0.0 - 100.0 0 40412
DO1 output limit (upper) 0.0 - 100.0 1000 40413
DO1 limit type 0: Lower limit -3%, Upper limit 103%
1: Lower limit, Upper limit 103%
2: Lower limit -3%, Upper limit
3: Lower limit, Upper limit
0 40414
DO2 output type 0: Event output
1: Control output
0 40415
*
DO2 master St. No. 0-255 0 40416
*
DO2 master Ch. No. 1-4 1 40417
*
DO2 BIT position 0-FFFF 2 40418
DO2 output option 0-15 0 40419
DO2 output logic operation AND 0-00FF 0 40421
DO2 output logic operation OR 0-00FF 0 40422
DO2 scaling base -100.0 - +100.0 0 40423
DO2 scaling span -100.0 - +100.0 1000 40424
DO2 proportion cycle 1-120 30 40425
DO2 output limit (lower) 0.0 - 100.0 0 40426
DO2 output limit (upper) 0.0 - 100.0 1000 40427
DO2 limit type 0-3 0 40428
DO3 output type 0: Event output
1: Control output
0 40429
*
DO3 master St. No. 0-255 0 40430
*
DO3 master Ch. No. 1-4 1 40431
*
DO3 BIT position 0-FFFF 4 40432