5.6 Setting/Monitor Area Entry Numbers (Control module)
Confi guration Parameters
Contents
Reading out/Writing
data setting range
Depends
on Input
range
Factory-set
value
Register
No.1
(Ch1)
Register
No.2
(Ch2)
Register
No.3
(Ch3)
Register
No.4
(Ch4)
Entry
ban
Control when burnout is
detected
0: Stop control
1: Continue control
0 (Stop control) 41407 42407 43407 44407
LED2 Lamp Confi guration 0 to 255 1 40222
*
LED3 Lamp Confi guration 0 to 255 12 40223
*
LED4 Lamp Confi guration 0 to 255 13 40224
*
LED5 Lamp Confi guration 0 to 255 14 40225
*
LED6 Lamp Confi guration 0 to 255 15 40226
*
Reset main unit 0: Do nothing
1: Reset main unit
0 40101
*
Monitor Parameters
Note
Monitor parameter can be entered to the monitor area only. Do not enter it to the setting area.
Contents
Reading out/Writing
data setting range
Depends
on Input
range
Factory-set
value
Register
No.1
(Ch1)
Register
No.2
(Ch2)
Register
No.3
(Ch3)
Register
No.4
(Ch4)
Entry
ban
SV value 0 to 100% FS
c
- 30905 30906 30907 30908
Remote mode switch 0: Local
1: Remote
- 30030
31037
30031
32037
30032
33037
30033
34037
System time 0 to 65535 - 30001
Measurement value (PV) -5 to 105% FS - 30002
31001
30003
32001
30004
33001
30005
34001
Measurement value (SV) 0 to 100% FS - 30006
31002
30007
32002
30008
33002
30009
34002
DV -105 to 105% FS - 30010
31003
30011
32003
30012
33003
30013
34003
Output value (MV1) -3.0 to 103.0% - 30014
31004
30016
32004
30018
33004
30020
34004
Output value (MV2) -3.0 to 103.0% - 30015
31005
30017
32005
30019
33005
30021
34005
Remote SV (RSV) 0.0 to 100.0% FS - 30022
31045
30023
32045
30024
33045
30025
34045
RCJtemp -3276.7 to
3276.7°C
- 30110
31016
30111
32016
30112
33016
30113
34016
Heater current [A] 0.0 to 50.0A - 30071
31046
30073
32046
30075
33046
30077
34046
Heater current [B] 0.0 to 50.0A - 30072
31047
30074
32047
30076
33047
30078
34047
Leak current [A] 0.0 to 50.0A - 30081
31048
30083
32048
30085
33048
30087
34048