User`s manual

5-58 INP-TN5A0202-E
5.6 Setting/Monitor Area Entry Numbers (Control module)
Alarm Parameters
Contents
Reading out/Writing
data setting range
Depends
on Input
range
Factory-set
value
Register
No.1
(Ch1)
Register
No.2
(Ch2)
Register
No.3
(Ch3)
Register
No.4
(Ch4)
Entry
ban
ALM1 hysteresis 0 to 50% FS
c
1°C 41035 42035 43035 44035
ALM1 delay time 0 to 99min.59sec.
/ 0 to 99hr.59min.
0 41037 42037 43037 44037
ALM1 delay time units 0: sec.
1: min.
0 (sec.) 41038 42038 43038 44038
ALM2 hysteresis 0 to 50% FS
c
1°C 41043 42043 43043 44043
ALM2 delay time 0 to 99min.59sec.
/ 0 to 99hr.59min.
0 41045 42045 43045 44045
ALM2 delay time units 0: sec.
1: min.
0 (sec.) 41046 42046 43046 44046
ALM3 hysteresis 0 to 50% FS
c
1°C 41051 42051 43051 44051
ALM3 delay time 0 to 99min.59sec.
/ 0 to 99hr.59min.
0 41053 42053 43053 44053
ALM3 delay time units 0: sec.
1: min.
0 (sec.) 41054 42054 43054 44054
ALM4 hysteresis 0 to 50% FS
c
1°C 41059 42059 43059 44059
ALM4 delay time 0 to 99min.59sec.
/ 0 to 99hr.59min.
0 41061 42061 43061 44061
ALM4 delay time units 0: sec.
1: min.
0 (sec.) 41062 42062 43062 44062
ALM5 hysteresis 0 to 50% FS
c
1°C 41067 42067 43067 44067
ALM5 delay time 0 to 99min.59sec.
/ 0 to 99hr.59min.
0 41069 42069 43069 44069
ALM5 delay time units 0: sec.
1: min.
0 (sec.) 41070 42070 43070 44070
Object Ch. No.
for interchannel ALM1
1 to 4 1 41039 42039 43039 44039
Object Ch. No.
for interchannel ALM2
1 to 4 1 41047 42047 43047 44047
Object Ch. No.
for interchannel ALM3
1 to 4 1 41055 42055 43055 44055
Object Ch. No.
for interchannel ALM4
1 to 4 1 41063 42063 43063 44063
Object Ch. No.
for interchannel ALM5
1 to 4 1 41071 42071 43071 44071
CT[A]HB alarm set value 0.0 to 50.0(A) 0 41072 42072 43072 44072
CT[A]HB alarm hysteresis 0.0 to 50.0(A) 0.5 41073 42073 43073 44073
CT[A]HB load short-circuit
alarm set value
0.0 to 50.0(A) 0 41074 42074 43074 44074
CT[A]HB load short-circuit
alarm hysteresis
0.0 to 50.0(A) 0.5 41075 42075 43075 44075
CT[B]HB alarm set value 0.0 to 50.0(A) 0 41076 42076 43076 44076
CT[B]HB alarm hysteresis 0.0 to 50.0(A) 0.5 41077 42077 43077 44077
CT[B]HB load short-circuit
alarm set value
0.0 to 50.0(A) 0 41078 42078 43078 44078
CT[B]HB load short-circuit
alarm hysteresis
0.0 to 50.0(A) 0.5 41079 42079 43079 44079
Loop break detection time 0 to 9999sec 0 (Off) 41080 42080 43080 44080
Loop break detection band 0 to 100% FS
c
2.5% FS 41081 42081 43081 44081